16

CTB1-8 through CTB1-9

Drive Program Jumper. These positions come with a jumper from the factory
to allow testing of the drive with the Test/Isolate/Normal selector switch. When

the Test/Isolate/Normal switch is placed in the “Test” position, AC input power

will be applied to the drive and it will run at a speed determined by the position

of the H-O-A switch. However, some inverter function codes cannot be

changed with a run command issued to the drive. Therefore removal of this

jumper and the

Test/Isolate/Normal switch in the “Test” mode prevents the drive from running

and allows all function codes to be accessible.


CTB1-10 through CTB1-12

Drive Fault Contacts. Provides customer with a drive fault status via contact
closure. Form C contacts are rated 5A @ 240V AC, 24 VDC.


CTB1-13 through CTB1-15

Drive Run Contacts. Provides customer with a drive running status via contact
closure. Form C contacts are rated 5A @ 240V AC, 24 VDC


CTB1-16 through CTB1-17

HOA – Hand status for customer


CTB1-18 through CTB1-19

HOA – Auto status for customer


CTB1-20 through CTB1-22

Analog Speed Reference Input. Connect customer supplied 0-10 VDC or 4-20
mA “Auto” speed reference signal. This signal functions as the drive’s speed

reference when the H-O-A switch is in the “Auto” position. If utilizing a 0-10 VDC

signal, CTB1-20 and CTB1-22 are to be used. If utilizing a 4-20 mA signal, CTB1-

20 and CTB1-21 are to be used. CTB1-20 is the common terminal for either

input signal. See the customer interface diagram for details. Ground bar

provided for cable shield grounding.


CTB1-24 through CTB1-26

Drive Run Contacts. Provides customer with a drive running status via contact
closure. Form C contacts are rated 5A @ 240V AC, 24 VDC


CTB1-27
through CTB1-28

Analog Output. The analog output is a 0/4-20 mA and is shipped from the
factory disabled. Ground bar provided for cable shield grounding.


CTB1-29 through CTB1-30

Drive/Off/Bypass – Bypass status for customer


CTB1-31
through CTB1-32

Enable Input. These positions come with a jumper from the factory. Put
normally open enable contacts between CTB1-31 and CTB1-32. Closure

between the contacts is required for the motor to run in either drive or Bypass

mode.


CTB1-33
through CTB1-34

Motor Space heater. 120V AC power is available for Motor space heater with
an extra VA CPT.


CTB1-35
through CTB1-36

Remote Bypass. Put normally open remote bypass contacts between CTB1-35
and CTB1-36. Closure between these positions allow for remote bypassing the

drive in the event of a drive fault. After the drive reports a fault condition a



DEH40652

– Page 9

AN 11-2021 Rev 06, 12/16/2011