Table – 3 (575V)
Device
AF - 600 Hp
Rating(s)
Minimum Wire
Size
Maximum Wire
Size
Required Torque
Load Reactor (6KFP Series)
1 through 5
# 22 AWG
# 10 AWG
4.5 lb. in.
7.5 through 20
# 14 AWG
# 6 AWG
16 lb. in.
25 through 40
# 18 AWG
# 4 AWG
16 lb. in.
50 through 100
# 6 AWG
1/0
45 (6 - 4AWG), 50 (2-1/0
AWG)
Load Reactor (6KFP*L Series) -
3% Z
1 through 10
# 22 AWG
# 10 AWG
4.5 lb. in.
15 through 20
# 14 AWG
# 6 AWG
16 lb. in.
25
# 18 AWG
# 4 AWG
16 lb. in.
30 through 75
# 6 AWG
# 1/0
45 (6 - 4AWG), 50 (2-1/0
AWG)
100 through 600
Note 2
Note 2
Note 1
Load Reactor (6KFP*L Series) -
1% Z
1 through 10
# 22 AWG
# 10 AWG
4.5 lb. in.
15 through 20
# 14 AWG
# 6 AWG
16 lb. in.
25
# 22 AWG
# 14 AWG
16 lb. in.
30
# 14 AWG
# 6 AWG
16 lb. in.
40 through 75
# 6 AWG
# 1/0
45 (6 - 4AWG), 50 (2-1/0
AWG)
100 through 600
Note 2
Note 2
Note 1
Control Terminal Board
2 through 100
# 26 AWG
# 10 AWG
Note 1
Note (1): For unmentioned torques, Refer UL508A tables in tab "UL508A" in the same excel file
Note (2): The input and output terminals have Busbars provision for motor connections.