GE Industrial Solutions AF-650 GP Drive Panel User Manual

Page 48

Advertising
background image

48

Table – 1 (208V)

Device

AF - 600 Hp Rating(s) Minimum Wire Size Maximum Wire Size Required Torque

NON FUSED DISCONNECTOR

AND FUSE BLOCK

2-5

# 14 AWG

# 4 AWG

Note 1

7.5-10

# 14 AWG

# 4 AWG

Note 1

15-20

# 8 AWG

1/0

Note 1

25-30

# 8 AWG

1/0

Note 1

40-60

# 4 AWG

300 MCM

Note 1

FUSED DISCONNECTOR

1 through 15

# 10 AWG

# 3 AWG

Note 1

20

# 14 AWG

# 2/0 AWG

Note 1

25 through 50

# 6 AWG

# 3/0 AWG

Note 1

60

# 2 AWG

600MCM

Note 1

Circuit Breaker

1 through 30

# 12 AWG

# 3/0 AWG

Note 1

40 through 60

# 8 AWG

350 MCM

Note 1

Overload Relay

1 through 10

# 14 AWG

# 8 AWG

20 lb. in.

15 through 30

# 10 AWG

# 3 AWG

50 lb. in.

40 through 50

# 6 AWG

250 MCM

275 lb. in., Note 2

60

# 6 AWG

350 MCM

200 lb. in., Note 2

Drive output power Terminal

Board

1 through 5

# 24 AWG

# 10 AWG

5.3 lb.in.

7.5 through 10

# 6 AWG

# 6 AWG

16 lb.in.

15 through 20

# 2 AWG

# 2 AWG

40 lb.in.

25 through 30

3/0

3/0

89 lb.in.

40 through 60

4/0

4/0

212 lb.in.

Load Reactor (6KFP Series)

1 through 2

# 22 AWG

# 10 AWG

4.5 lb.in

3 through 10

# 14 AWG

# 6 AWG

16 lb.in

15 through 30

# 6 AWG

1/0

45 lb.in (6 - 4AWG),

50 lb.in (2-1/0 AWG)

40

# 2 AWG

4/0

150 lb.in

50 through 60

Note 2

Note 2

Note 1

Load Reactor (6KFP*L

Series) - 3% Z

1 through 3

# 22 AWG

# 10 AWG

4.5 lb.in

5

# 14 AWG

# 6 AWG

16 lb.in

7.5

# 22 AWG

# 14 AWG

16 lb.in

10

# 14 AWG

# 6 AWG

16 lb.in

15 through 25

# 6 AWG

1/0

45 lb.in (6 - 4AWG),

50 lb.in (2-1/0 AWG)

30 through 60

Note 2

Note 2

Note 1

Control Terminal Board

1 through 60

# 26 AWG

# 10 AWG

Note 1

Note (1): For unmentioned torques, Refer UL508A tables in tab "UL508A" in the same excel file
Note (2): The input and output terminals have Busbars provision for motor connections.



DEH40653

– Page 2

AN 12-1007 Rev 05, 04/04/2012