Harmonic Filter

When the panel is provided with the Harmonic filter, Make sure to set the timer
(CITMR) based on motor starting characteristics to bring the capacitor into the

power circuit through capacitor switching contactor C1.(Factor setting will be 30

sec)


Output contactor

When the panel is provided with output contactor option, M2 (Load contactor)
will be wired at the line side of the motor.


Emergency Stop

This operator is used to shut off the panel output in case of Emergency.

To restart the panel, Reset the E-stop by turn to release.


Power On
Indicator

This white light on the panel door indicates that the circuit breaker/disconnect
switch is closed and that AC power is present at the panel input terminals.

Absence of light from this indicator when it should be “ON” may indicate the

presence of a blown fuse(s) on the primary or secondary of the control power

transformer or a blown bulb.


Normal Indicator

This operator and functionality is only available on the 3 Contactor Bypass
Panel.

This green light on the panel door indicates that AC input power is being applied

to the drive input terminals. This indicating light will energize when the input

contactor is energized and the Test/Isolation/Normal switch is in “Normal.


Enable Indicator

This clear light on the panel door indicates that the customer interlock circuit is
closed and the system is ready for the motor to be energized. Note, with the

customer safety interlock circuit open the panel will not allow output power to

the motor in either “Bypass” or “Drive”.

Drive Run Indicator

This optional green light on the panel door indicates that the drive output
contactor is energized and the drive will output power to the motor. The

conditions that will cause this light to become energized are - Drive/Off/Bypass

and Test/Isolate/Normal switches are in the “Drive” and “Normal” positions

without the drive reporting a fault condition. Note that this light only means

that the drive output contactor is energized and the panel is operating in “Drive”

mode. If the motor’s shaft is not rotating then it may be due to 1) no run

command provided to the drive (i.e. H-O-A switch in the “Off” position) 2) No

Speed ref. 3) an open load side disconnect (external to drive panel).

Bypass Run Indicator

This blue light on the panel door indicates that the bypass contactor is
energized and therefore that 50 or 60 cycle AC line power is being applied to

the motor. In order for this to happen the Drive/Off/Bypass selector must be in

the “Bypass” position and the H-O-A switch must be in either the “Hand” or

“Auto” positions (if “Auto” then remote run contacts must also be closed). Note

that bypass operation can also occur in “Drive” mode if the drive has tripped



DEH40652

– Page 6

AN 11-2021 Rev 06, 12/16/2011