3. AF 650 GP Drive Terminal Board I/O

Any of the AF 650 GP terminal board I/O points which are not already in use for proper operation of the bypass

panel are available for customer use. The meanings and connection diagrams for these I/O points are well

described and illustrated in the AF 650 GP User’s Guide (DET607 – For up to 50HP@208V and up to

100HP@460/575V or DET608 - For 125HP and above @ 460/575V) which is supplied with your panel

documentation package. However there are several I/O points, which will find frequent use in bypass panel

applications that they are described below for convenience. Refer to user’s guide DET – 607 or DET – 608 for

terminal locations. Refer to section 2 and wiring diagram for details on correct connection points

39 & 42

4-20 mA output signal will be available from the drive at terminal 39 and
42


Relay 1 – 01,02,03

Normally open inverter fault contacts. These contacts are utilized to energize
an interposing relay for bypass panel control logic and to provide customers

with a drive fault status via higher rated normally open contacts than those

inherent to the drive.


Relay 2 – 04,05,06

Normally open programmable contacts. These contacts have been configured
to provide a drive running status for customer use. This status is then used to

energize an interposing relay to provide customers with drive running status via

higher rated normally open contacts than those inherent to the drive. .


54, 55

Used for drive speed reference inputs


29

Jog (Digital input)
Drive will be programmed (Parameter C20) to run at preset speed (50Hz jog

frequency)


1,2

EtherNet.


62,63,66,67,CS

ProfiBus DP/BACNET Communications (with option card)


68,69,61

ModBus RTU / RS485 Port


39,42

Analog output


X30, 1 –12

1) Encoder module
2) Additional I/P and O/P (General purpose I/O) (24V DIO, 0-10V Input,

4-20 mA AO)


X32, 1 –12

Resolver module

18,19

18 -> Start

19 -> Reverse

ProfiNet RT

ModBus TCP

DEH40652