Because instantaneous trip circuit breakers are so fast acting, the NEC actually

allows trip level settings up to 1300% of motor FLA if it can be shown to be

required by engineering evaluation. When a motor is started across the AC line

it can draw a very large peak current for the first half-cycle which can cause

nuisance tripping in instantaneous trip breakers set at 700%. GE Motors &

Industrial Systems has conducted analyses which show that certain models can

require this 1300% trip level to avoid nuisance tripping on across-the-line starts.

Generally the trip level will need to be higher for premium efficiency motors than

for standard efficiency ones.

In panels not requiring bypass the AF-650 GP drive essentially “soft-starts” the

motor by increasing the output voltage and frequency. Therefore high motor

inrush currents will not occur and should not be an issue. However, the rating

plugs for the circuit breakers in the AF-650 GP panels have been chosen to

allow trip level settings up to 13 times the current ratings of the panel. If the trip

level is set at 13 times the panel rated current and the circuit breaker still trips it

is probably due line conditions affect how the DC capacitor bank charges upon

applying AC power. The drive inherently contains a charge limiting circuit but in

a very small number of circumstances, the inrush may cause the circuit breaker

to trip even at a setting of 13 time the panel rating. If this is the case, possible

corrective actions are:

1) Check the trip setting in the rating plug

2) Make sure there is not an actual short causing the trip.

3) Try closing the breaker several times. Actual inrush is dependant on line

conditions when the breaker is closed. Closing the breaker when line

conditions are acceptable should prevent tripping.

4) Since actual inrush is dependant on the line conditions, correct the line

condition is the causing excessive inrush.

5) Try another rating plug. Perhaps the tolerances on the one included with

your breaker are unfavorable.

6) Add an AC Line Reactor to the input of the drive, which increases input

impedance and decreases the input current.







DEH40658

– Page 9