5. AF-650 GP Drive Function Code Changes
The following section does not apply to the Disconnect Drive Panels. All programmable functions are at the
drive’s factory defaults.
The AF 650 GP Adjustable Frequency Drive has programmable functions. A complete description of these
function codes can be found in DET – 607 or DET – 608 manuals. The purpose of this section is to identify those
function codes which changed from the factory drive defaults for panel installation.
Live Zero Time Out Time
(AN00)
Set to “10” seconds
Live Zero Time Out Function (AN01)
Set to “3” Jogging
Terminal 53 Live Zero
(AN17)
Set to “0” Disabled
Terminal 54 Live Zero
(AN27)
Set to “1” Enabled
Jog Speed
(C20)
Set to “50” Hz
Frequency Command 2
(C30)
Set to “2” Analog Input 54
Terminal 27 Digital Input
(E03)
Set to “2” Coast inverse
Terminal 32 Digital Input
(E05)
Set to “14” Jog
Terminal 33 Digital Input
(E06)
Set to “6” Stop Inverse
Relay 1
(E24)
Set to “9” Alarm
Relay 2
(E24)
Set to “5” Running
Electronic Overload
(F10)
Set to “4” Elec OL Trip 1
Motor Thermistor Input
(F12)
Set to “0” None
Auto-Reset (Times)
(H04)
Set to “13” Infinite Auto Reset
Reverse lock
(H08)
Set to “2” (To enable reverse direction run command)