5. AF-650 GP Drive Function Code Changes

The following section does not apply to the Disconnect Drive Panels. All programmable functions are at the

drive’s factory defaults.

The AF 650 GP Adjustable Frequency Drive has programmable functions. A complete description of these

function codes can be found in DET – 607 or DET – 608 manuals. The purpose of this section is to identify those

function codes which changed from the factory drive defaults for panel installation.


Live Zero Time Out Time

(AN00)

Set to “10” seconds


Live Zero Time Out Function (AN01)

Set to “3” Jogging


Terminal 53 Live Zero

(AN17)

Set to “0” Disabled


Terminal 54 Live Zero

(AN27)

Set to “1” Enabled


Jog Speed

(C20)

Set to “50” Hz


Frequency Command 2

(C30)

Set to “2” Analog Input 54


Terminal 27 Digital Input

(E03)

Set to “2” Coast inverse


Terminal 32 Digital Input

(E05)

Set to “14” Jog


Terminal 33 Digital Input

(E06)

Set to “6” Stop Inverse


Relay 1

(E24)

Set to “9” Alarm


Relay 2

(E24)

Set to “5” Running


Electronic Overload

(F10)

Set to “4” Elec OL Trip 1


Motor Thermistor Input

(F12)

Set to “0” None


Auto-Reset (Times)

(H04)

Set to “13” Infinite Auto Reset


Reverse lock

(H08)

Set to “2” (To enable reverse direction run command)

Drive Programming


Loss of reference control – Run at preset speed
Loss of reference control option is not available in Disconnect Drive Panels

Main Menu

Parameter data set

Down arrow

DEH40658

– Page 10