coordination issues. Therefore if it is necessary to change the input fuses,

please consult your preferred fuse supplier and/or your local GE starter

distributor for Type 2 and overload relay coordination.


Circuit Breaker Trip Level

The optional circuit breaker in the AF 650 GP & Bypass panel is a solid state
Spectra RMS

TM

molded case circuit breaker from GE. The purpose of the circuit

breaker is to provide short circuit protection and over current for the panel

components, field wiring and the motor. The breaker uses a solid state sensing

element which calculates the true RMS

TM

value of the current every cycle,

resulting in a tripping action which is very fast. For this reason the NEC allows

the trip level to be set at 700% of the motor FLA to allow for the high locked

rotor current which the motor draws during across-the-line starts (see NEC

section 430-52 and Table 430-152 of the NEC). Because instantaneous trip

circuit breakers are so fast acting, the NEC actually allows trip level settings up

to 1300% of motor FLA if it can be shown to be required by engineering

evaluation. When a motor is started across the AC line it can draw a very large

peak current for the first half-cycle which can cause nuisance tripping in

instantaneous trip breakers set at 700%. GE Motors & Industrial Systems has

conducted analyses, which show that certain models can require this 1300%

trip level to avoid nuisance tripping on across-the-line starts. Generally the trip

level will need to be higher for premium efficiency motors than for standard

efficiency ones.

The rating plugs for the circuit breakers in the AF 650 GP & Bypass panels have

been chosen to allow trip level settings up to 13 times the current ratings of the

panel. If the trip level is set at 13 times the motor FLA and the circuit breaker

still trips it is probably due to the fact that your motor has very high efficiency

and therefore exhibits the highest inrush currents. Possible corrective actions

are:

1. Check the trip setting in the rating plug

2. Make sure there is no actual short causing the trip.

3. Try closing the breaker several times. Actual inrush is dependant on line

conditions when the breaker is closed. Closing the breaker when line

conditions are acceptable should prevent tripping.

4. Since actual inrush is dependant on the line conditions, correct the line

condition is the causing excessive inrush.

5. Try another rating plug. Perhaps the tolerances on the one included with

your breaker are unfavorable.

6. Start the motor with drive mode.

7. For NEMA E motors (super premium efficiency) the NEC 1996 version will

allow a trip setting of 1700% of motor FLA.

Motor Overload Trip Level

The overload relay in your AF 650 GP & Bypass panel is the C-2000

TM

Class 20

or Class 30 fixed heater type from GE which is panel mounted. Class 30

overload relays are utilized for panels rated 60Hp and above at 208 VAC plus

150Hp and above at 460 VAC. The overload relay carries all motor current

whether it is running from the drive or across the AC line (bypass mode).

Whereas the panel circuit breaker or input fuses is intended to provide short

circuit protection for the panel components, field wiring and the motor, the

overload relay’s function


DEH40652

– Page 13