Table – 3 (575V)

Device

AF - 600 Hp

Rating(s)

Minimum Wire

Size

Maximum Wire

Size

Required Torque

NON FUSED DISCONNECTOR

AND FUSE BLOCK

1 through 10

# 14 AWG

# 4 AWG

Note 1

15 through 40

# 14 AWG

# 4 AWG

Note 1

50 through 60

# 8 AWG

1/0

Note 1

75 through 100

# 8 AWG

1/0

Note 1

FUSED DISCONNECTOR

1 through 40

# 10 AWG

# 3 AWG

Note 1

50 through 60

# 14 AWG

# 2/0 AWG

Note 1

75 through 125

# 6 AWG

# 3/0 AWG

Note 1

150 through 300

# 2 AWG

600MCM

Note 1

350 through 600

2 X # 2 AWG

2 X 600MCM

Note 1

Circuit Breaker

1 through 75

# 12 AWG

# 3/0 AWG

Note 1

100 through 200

# 8 AWG

350 MCM

Note 1

250 through 400

2 X 2/0

2 X 500 MCM

Note 1

250 through 400

#8 AWG

600 MCM

Note 1

500 through 600

3X #3/0 AWG

3X 500 MCM

Note 1

Overload Relay

2 through 25

# 14 AWG

# 8 AWG

20 lb. in.

30 through 75

# 10 AWG

# 3 AWG

50 lb. in.

100

# 6 AWG

250 MCM

275 lb. in.

Drive output power Terminal

Board

1 through 10

# 24 AWG

# 10 AWG

5.3 lb.in.

15 through 20

# 6 AWG

# 6 AWG

16 lb.in.

25 through 40

#2 AWG

#2 AWG

40 lb.in.

50 through 60

#1 AWG

#1 AWG

89 lb.in.

75

4/0

4/0

212 lb.in.

100

300MCM

300MCM

212 lb.in.

125 through 150

2 x 2/0

2 x 2/0

Note1, 2

200 through 350

2 x 350MCM

2 x 350MCM

Note1, 2

400 through 600

4 x 500MCM

4 x 500MCM

Note1, 2

Continued…