6. Troubleshooting
Auto-Tune
In the event that it is desired to “auto-tune” the drive to the connected motor, reference the following
instructions along with the AF-650 GP User’s Guide (DET – 607 or DET - 608):
With power applied to the panel –
1) Place the Hand/Off/Auto selector switch in the “Off” position. (Need to make sure the drive is energized
but not in a run state).
2) For Full Auto tuning follow the instruction below
Quick Menu
Ok
Quick start
Ok
Once Up arrow
Ok
P-04 Auto Tuning
Ok
[1] Full Auto tune
Ok
Follow the Keypad direction
Note: If the panel has a load reactor, select “Reduced Auto tune”.