Hand/Off/Auto
Selector

This selector is also referred to as the H-O-A switch. In the “Off” position power
will be removed from the motor in both bypass and drive modes of operation. It

should be noted that this will not cause AC input power to be removed from the

drive. To remove drive input power the Test/Isolate/Normal switch, If Provided

should be placed in the “Isolate” position.

In “Hand” mode, power will be applied to the motor from either the drive or the

AC line according to the Drive/Off/Bypass selector. In this mode the inverter’s

frequency reference is determined by the position of the speed pot on the panel

if ordered.

In “Auto” mode, power will be applied to the motor only when a connection is

made between the two remote run contacts on the customer terminal board

inside the panel enclosure. In this mode the inverter’s frequency reference is

determined by a customer supplied 0-10 VDC or 4-20 mA signal.

Hand - Off - Auto on Drive Keypad

All AF-600 FP Drive Panels include a keypad for programming and operation of

the drive and includes Hand, Off, and Auto operation keys / buttons. When

shipped from the factory, the Hand, Off and Auto buttons are enabled .

Pressing the Off button while the drive is running will cause the drive to

decelerate and shut off regardless of the positions of the panel’s selector

switches. To resume normal operations (that is control the unit from its selector

switches and analog signal) press the Auto Button one time.

For more details on the Hand, Off, and Auto operation keys, refer to manuals

DET-620


Emergency Stop

This operator is used to shut off the panel output in case of Emergency.

To restart the panel, Reset the E-stop by turn to release.


Power On Indicator

This white light on the panel door indicates that the circuit breaker/disconnect
switch is closed and that AC power is present at the panel input terminals.

Absence of light from this indicator when it should be on may indicate the

presence of a blown fuse(s) on the primary or secondary of the control power

transformer or a blown bulb.


Normal Indicator

This operator and functionality is only available on the 3 Contactor Bypass
Panel.

This green light on the panel door indicates that AC input power is being applied

to the drive input terminals. This indicating light will energize when the input

contactor is energized and the Test/Isolation/Normal switch is in “Normal.


DEH40602

– Page 5

AN 11-2021 Rev 05, 12/15/2011

WARNING: Enabling and using the Hand operation key may cause

control inputs to drive to be ignored and may result in unintended
operations / starting of the drive unit.