6. Troubleshooting


In the event that it is desired to “auto-tune” the drive to the connected motor, reference the following

instructions along with the AF-600 FP User’s Guide (DET – 609 or DET - 610):

With power applied to the panel –

1) Place the Hand/Off/Auto selector switches in the “Off” positions respectively. (Need to make sure the

drive is energized but not in a run state)

2) For Full Auto tuning follow the instruction below

Quick Menu

Ok

Quick start

Ok

Once up arrow

Ok

P-04 Auto Tuning

Ok

[1] Full Auto tune

Ok

Follow the Keypad direction

Note: If the panel has a load reactor, select “Reduced Auto tune”.