Use 3/8-16 Hardware’s for all slim line wall mount enclosures and 1/2-13 Hardware’s

for all Standard Wall mount and Floor mount enclosures mounting to fulfill Seismic

Requirements


For NEMA 12 enclosure types, liquid tight conduit and fittings shall be installed to

maintain the enclosure integrity.


GROUNDING


All field wiring shall be copper and have a minimum insulation rating of 75

C (167

F).

Size grounding conductors according to local and national codes.

Each panel contains a grounding bus with provisions for connecting a field-grounding

conductor.

All panels/enclosures must be grounded.

Grounding methods must comply to local and national codes.

POWER WIRE

(Greater than 120 VAC)


All field wiring shall be copper and have a minimum insulation rating of 75

C (167

F).

Size all wire based on panel nameplate current ratings in accordance with local and

national codes. Do not use the cable sizes listed in DET - 609 & DET - 610.

All power wiring must be routed away from other wiring. Avoid running power wiring

parallel to other wiring without a minimum separation distance of four (4) inches.

Power wiring should only cross perpendicular to other wiring.

Input and output power shall be connected as per the wiring diagram.

Incoming power cables should be terminated at line side of the lugs provided with the

Circuit breaker or Disconnect switch.

Locate terminals (T1, T2, and T3) in the panels and use these terminals to connect the

motor wires. Depending on actual drive panel configuration, motor cables should be

terminated on the load side lugs provided with the core drive (Disconnect drive or non-

bypass panel without load reactor), load reactor (Disconnect drive or non-bypass panel

with load reactor), contactor (non-bypass panel with load contactor) or overload relay

(all Bypass contactor configurations).



DEH40600

– Page 3

AN 12-1007 Rev 05, 04/04/2012

CAUTION: Failure to cover components from metal shavings may result in
damage to equipment.