Adjustments – GE Industrial Solutions AF-600 FP Drive Panel User Manual

Page 19

Advertising
background image

19

4. Adjustments

The AF 600 FP & Bypass panel has several user settable adjustments, which allow it to be tailored specifically

for your 3-phase induction motor. Setting these adjustments appropriately is an important factor in ensuring

that applicable safety codes are met and that your bypass panel, wiring, and motor are adequately protected.

The following list comprises all of the user adjustable devices/components inside the AF 600 FP & Bypass

panel. The user may wish to have a copy of NFPA 70-2008 (commonly known as the National Electric Code or

simply NEC) available for reference when setting these adjustments.



Input Fuses

Main input fuses are provided standard with your AF 600 FP & Bypass panel. In
general there are two configurations that utilize input fuses; 1) input disconnect

with load side separately mounted fuses and 2) input Fused Disconnect where

the fuses are an integral part of the disconnect. If your panel was ordered with

the circuit breaker option, the disconnect device and fuses are replaced by the

circuit breaker. The main input fuses provided with your bypass panel has been

closely coordinated to provide short circuit protection for the inverter along

with short circuit and over current protection for the motor. In “Drive” mode of

operation, the fuses only provide short circuit protection due to the fact that the

inverter has inherent over current protection. In “Bypass” mode of operation,

the fuses provide both short circuit and over current protection for the motor.

UL listed Class J time-delay fuses are provided with your panel. These fuses

have been sized in accordance to NEC section 450-52 and Table 450-152. NEC

states fuses of this type are to be sized at 175% of motor full-load amps (FLA).

Due to the fact that actual motor FLA along with starting current requirements

vary between manufacturer and motor types the fuses provided are based on

standard NEC motor data. Verify that actual motor FLA * 1.75 is equal to or

greater than the input fuse amp rating. In the case where the actual motor FLA

* 1.75 is less than the provided fuses amp rating then smaller fuses may need

to be installed to be in compliance with NEC section 430-52 and Table 430-152.

Please note exception 1 to NEC 430-52, which states that where the calculated

fuse amp rating does not correspond to a standard fuse size the next higher

standard fuse size may be used. In cases where the fuses provided is not

sufficient for the starting current requirements of the motor, please note

exception 2-b to NEC 430-52. Exception 2-b states the rating of a time-delay

fuse may be increased but shall not exceed 225% of the motor FLA in any case.

In the case where a larger or smaller fuse is required, a limiting factor in the

bypass panel may be the fuse holder. The appendices provide a table for the

maximum fuse size permitted in the existing fuse holder.

Coordinating the fuses for the bypass starter is the over current protection

coordination between the Class 20/30 overload relay and the fuse’s over

current protection. This coordination is to avoid nuisance blowing of fuses.

Coordination between the inverter’s short circuit rating and the fuse’s rms let

through currents during a short circuit condition has also been closely

evaluated. Changing the main input fuses may impact one or both of the

above coordination issues. Therefore if it is necessary to change the input

DEH40602

– Page 12

AN 11-2021 Rev 05, 12/15/2011

Advertising