GE Industrial Solutions AF-600 FP Drive Panel User Manual

Page 16

Advertising
background image

16







CTB1-10
through CTB1-12

Provides customer with a drive fault status via contact closure. Contacts are
rated 5A @ 240V AC, 24V DC.


CTB1-13 through CTB1-15

Provides customer with a drive running status via contact closure. Contacts are
rated 120/208 VAC or 30 VDC, 5 A.


CTB1-25
through CTB1-26

Place normally open contacts between CTB1-25 and CTB1-26. Closure
between these contacts cause the motor to run at a preset speed (speed

programmed by function code C20) or from the AC input power. The preset

speed command is issued if the Drive/Off/Bypass and Test/Isolate/Normal

selector switches are in “Drive” and “Normal” mode of operation, regardless of

the H-O-A switch position. If the Drive/Off/Bypass selector switch is the “Off”

position the motor will not run. A typical use for this input is a smoke purge

command.


CTB1-8 through CTB1-9

These positions come with a jumper from the factory to allow testing of the
drive with the Test/Isolate/Normal selector switch. When the

Test/Isolate/Normal switch is placed in the “Test” position, AC input power will

be applied to the drive and it will run at a speed determined by the speed pot or

the “Auto” speed reference, depending on the position of the H-O-A switch.

However, some inverter function codes can not be changed with a run

command issued to the drive. Therefore removal of this jumper and the

Test/Isolate/Normal switch in the “Test” mode allows all function codes to be

accessible.


CTB1-20 through CTB1-22

Connect customer supplied 0-10 VDC or 4-20 mA “Auto” speed reference signal.
This signal functions as the drive’s speed reference when the H-O-A switch is in

the “Auto” position. If utilizing a 0-10 VDC signal, CTB1-20 and CTB1-22 are to

be used. If utilizing a 4-20 mA signal, CTB1-20 and CTB1-21 are to be used.

CTB1-20 is the common terminal for either input signal. See the customer

interface diagram for details.


CTB1-31
through CTB1-32

These positions come with a jumper from the factory. Put normally open enable
contacts between CTB1-31 and CTB1-32.

Closure between the contacts is required for the motor to run in either drive or

Bypass mode.


CTB1-33 through CTB1-34

Smoke Purge circuit


CTB1-27 through CTB1-28

Analog output 0/4 – 20mA.




DEH40602

– Page 9

AN 11-2021 Rev 05, 12/15/2011

CAUTION: Jumpering CTB1-35 and CTB1-36 together will not allow for motor
flux to decay prior to applying AC line power to the motor in the event of a drive
fault. The absence of the 10-second time delay can result in a devastating
torque pulse which can damage your motor, driven load and/or installation. The
AF 600 FP & Bypass panel does not have a line synchronizing function to
permit a smooth switchover to AC line power, therefore a time delay is the only
way to ensure a safe transition.

NOTE: 4-20 mA output signal will be available from the drive at
terminal 39 and 42, which is wired for customer to terminal board
CTB1-27 and CTB1-28.