4. Adjustments

The AF-600 FP panel has several user settable adjustments which allow it to be tailored specifically for your 3-

phase induction motor. Setting these adjustments appropriately is an important factor in ensuring that

applicable safety codes are met and that your panel, wiring, and motor are adequately protected. The

following list comprises all of the user adjustable devices/components inside the AF-600 FP, Bypass &

Disconnect Drive Panels. The user may wish to have a copy of NFPA 70-2008 (commonly known as the

National Electric Code or simply NEC) available for reference when setting these adjustments.



Input Fuses

Main input fuses are provided standard with your AF-600 FP, Bypass &
Disconnect Drive Panels. In general there are two configurations that utilize

input fuses; 1) input disconnect with load side separately mounted fuses and 2)

input Fused Disconnect where the fuses are an integral part of the disconnect.

If your panel was ordered with the circuit breaker option, the disconnect device

and fuses are replaced by the circuit breaker. The main input fuses provided

with your panel has been closely coordinated to provide short circuit protection

for the inverter.

UL listed Class J time-delay fuses are provided with your panel. These fuses

have been sized in accordance to NEC section 450-52 and Table 450-152. NEC

states fuses of this type are to be sized at 175% of motor full-load amps (FLA).

Due to the fact that actual motor FLA along with starting current requirements

vary between manufacturer and motor types the fuses provided are based on

standard NEC motor data. Verify that the input fuse amp rating is less than or

equal to the actual motor FLA * 1.75. In the case where the actual motor FLA *

1.75 is less than the provided fuses amp rating then smaller fuses may need to

be installed to be in compliance with NEC section 430-52 and Table 430-152.

Please note exception 1 to NEC 430-52, which states that where the calculated

fuse amp rating does not correspond to a standard fuse size the next higher

standard fuse size may be used. In cases where the fuses provided is not

sufficient for the starting current requirements of the motor, please note

exception 2-b to NEC 430-52. Exception 2-b states the rating of a time-delay

fuse may be increased but shall not exceed 225% of the motor FLA in any case.

In the case where a larger or smaller fuse is required, a limiting factor in the

panel may be the fuse holder. The appendices provide a table for the

maximum fuses size permitted in the existing fuse holder. If these fuses shall

ever need to be replaced, refer for rating label located on the back of panel

cover.


Circuit Breaker Trip Level

The optional circuit breaker in the AF-600 FP HVAC panel is a solid state Spectra
RMS

TM

molded case circuit breaker from GE. The purpose of the circuit breaker

is to provide short circuit protection and over current for the panel components,

field wiring and the motor. The breaker uses a solid state sensing element

which calculates the true RMS

TM

value of the current every cycle, resulting in a

tripping action which is very fast. For this reason the NEC allows the trip level to

be set at 700% of the motor FLA to allow for the high locked rotor current which

the motor draws during across-the-line starts (see NEC section 430-52 and

Table 430-152 of the NEC).