GE Industrial Solutions AF-600 FP Drive Panel User Manual

Page 50

Advertising
background image

50

Table – 2 (460V)

Device

AF - 600 HP

Rating(s)

Minimum Wire Size Maximum Wire Size

Required

Torque

Load Reactor (6KFP

Series)

1 through 5

# 22 AWG

# 10 AWG

4.5 lb. in.

7.5 through 15

# 14 AWG

# 6 AWG

16 lb. in.

20 through 30

# 18 AWG

# 4 AWG

16 lb. in.

40 through 75

# 6 AWG

# 1/0

45 (6 - 4AWG),

50 (2-1/0 AWG)

100

# 2 AWG

# 4/0

150 lb. in.

125 through 300

Note 2

Note 2

Note 1

Load Reactor (6KFP*L

Series) - 3% Z

1 through 7.5

# 22 AWG

# 10 AWG

4.5 lb. in.

10 through 25

# 14 AWG

# 6 AWG

16 lb. in.

30 through 75

# 6 AWG

# 1/0

45 (6 - 4AWG),

50 (2-1/0 AWG)

100 through 600

Note 2

Note 2

Note 1

Load Reactor (6KFP*L

Series) - 1% Z

1 through 7.5

# 22 AWG

# 10 AWG

4.5 lb. in.

10 through 15

# 14 AWG

# 6 AWG

16 lb. in.

20

# 22 AWG

# 14 AWG

16 lb. in.

25

# 14 AWG

# 6 AWG

16 lb. in.

30 through 60

# 6 AWG

# 1/0

45 (6 - 4AWG),

50 (2-1/0 AWG)

75 through 600

Note 2

Note 2

Note 1

Control Terminal Board

2 through 300

# 26 AWG

# 10 AWG

Note 1

Note (1): For unmentioned torques, Refer UL508A tables in tab "UL508A" in the same excel file
Note (2): The input and output terminals have Busbars provision for motor connections.

















DEH40603

– Page 4

AN 12-1007 Rev 05, 04/04/2012