Table B
6KFP Series Non-Bypass Configuration -Electrical
Channel
HP Ratings
Estimated Watt Loss (Watts) at
208V
460V
575V
2
225
181
187
3
266
192
216
5
373
232
290
7.5
488
366
374
10
540
450
448
15
739
517
499
20
966
642
666
25
1133
764
734
30
1261
821
797
40
1863
1090
987
50
2034
1208
1147
60
2422
1336
1331
75
-
1719
1696
100
-
2101
2074
125
-
2256
2228
150
-
4283
4083
200
-
4977
-
250
-
5902
-
300
-
6770
-