Table B

6KFP Series Non-Bypass Configuration -Electrical

Channel

HP Ratings

Estimated Watt Loss (Watts) at

208V

460V

575V

2

225

181

187

3

266

192

216

5

373

232

290

7.5

488

366

374

10

540

450

448

15

739

517

499

20

966

642

666

25

1133

764

734

30

1261

821

797

40

1863

1090

987

50

2034

1208

1147

60

2422

1336

1331

75

-

1719

1696

100

-

2101

2074

125

-

2256

2228

150

-

4283

4083

200

-

4977

-

250

-

5902

-

300

-

6770

-