GE Industrial Solutions AF-600 FP Drive Panel User Manual

Page 49

Advertising
background image

49

Table – 2 (460V)

Device

AF - 600 HP

Rating(s)

Minimum Wire Size

Maximum Wire Size Required Torque

NON FUSED

DISCONNECTOR AND FUSE

BLOCK

1 through 10Hp

# 14 AWG

# 4 AWG

Note 1

15 through 30Hp

# 14 AWG

# 4 AWG

Note 1

40 through 50Hp

# 8 AWG

1/0

Note 1

60 through 75Hp

# 8 AWG

1/0

Note 1

100 through 125Hp

# 4 AWG

300 MCM

Note 1

150 through 300Hp

# 2 AWG

600 MCM

Note 1

FUSED DISCONNECTOR

1 through 30

# 10 AWG

# 3 AWG

Note 1

40 through 50

# 14 AWG

# 2/0 AWG

Note 1

60 through 100

# 6 AWG

# 3/0 AWG

Note 1

125 through 250

# 2 AWG

# 600MCM

Note 1

300 through 500

2 X # 2 AWG

2 X 600MCM

Note 1

550 through 600

4 X # 2 AWG

4 X 600MCM

Note 1

Circuit Breaker

1 through 75

# 12 AWG

# 3/0 AWG

Note 1

100 through 150

# 8 AWG

350 MCM

Note 1

200 through 350

2 X 2/0

2 X 500 MCM

Note 1

200 through 350

#8 AWG

600 MCM

Note 1

450 through 500

3X #3/0 AWG

3X 500 MCM

Note 1

550 through 600

4X #250 AWG

4X 500 MCM

Note 1

Overload Relay

2 through 25

# 14 AWG

# 8 AWG

20 lb. in.

30 through 75

# 10 AWG

# 3 AWG

50 lb. in.

100 through 125

# 6 AWG

250 MCM

275 lb. in., Note 2

150 through 250

# 6 AWG

350 MCM

200 lb. in., Note 2

300

# 8 AWG

500 MCM

375 lb. in., Note 2

Drive output power

Terminal Board

1 through 10

# 4 AWG

# 10 AWG

16 lb.in

15 through 25

# 10 AWG

# 7 AWG

16 lb.in

30 through 40

# 35 AWG

# 2 AWG

40 lb.in

50 through 75

# 50 AWG

1/0

89 lb.in

100

# 95 AWG

4/0

212 lb.in

125

# 120 MCM

250MCM

212 lb.in

150 through 200

2X2/0

2X2/0

Note 1, 2

250 through 350

2X350 MCM

2X350 MCM

Note 1, 2

450 through 600

4X500 MCM

4X500 MCM

Note 1, 2

Continued…









DEH40603

– Page 3

AN 12-1007 Rev 05, 04/04/2012

Advertising