GE Industrial Solutions AF-600 FP Drive Panel User Manual

Page 32

Advertising
background image

32


CTB1-27 through CTB1-28

Analog Output 0/4-20 mA.




CTB1-20 through CTB1-22

Connect customer supplied 0-10 VDC or 4-20 mA “Auto” speed reference signal.
This signal functions as the drive’s speed reference when the H-O-A switch is in

the “Auto” position. If utilizing a 0-10 VDC signal, CTB1-20 and CTB1-22 are to

be used. If utilizing a 4-20 mA signal, CTB1-20 and CTB1-21 are to be used.

CTB1-20 is the common terminal for either input signal. See the customer

interface diagram for details


CTB1-31
through CTB1-32

These positions come with a jumper from the factory. Put normally open enable
contacts between CTB1-31 and CTB1-32. Closure between the contacts is

required for the motor to run in either drive or Bypass mode.


CTB1-33
through CTB1-34

Smoke Purge circuit.


With Smoke purge option, After C20 Procedure follow below instruction

Smoke purge option is not available in Disconnect Drive Panels

Main menu
Parameter data set…with down arrow
Ok
E - ## Digital In/Out
Ok
E-0 # Digital Inputs
OK
Down arrow – 5 tines
Ok
SET TO [14] Jog
Ok








DEH40608

– Page 6

AN 11-2021 Rev 05, 12/15/2011

NOTE: 4-20 mA output signal will be available from the drive at terminal 39 and
42, which is wired for customer to terminal board CTB1-27 and CTB1-28.