5. AF 600 FP Drive Function Code Changes

The AF 600 FP Adjustable Frequency Drive has programmable function. A complete description of these

function codes can be found in DET – 609 or DET – 610. The purpose of this section is to identify those function

codes which changed from the factory defaults for bypass panel installation.


Live Zero Time Out Time

(AN00)

Set to “10” seconds


Live Zero Time Out Function (AN01)

Set to “3” Jogging


Terminal 53 Live Zero

(AN17)

Set to “0” Disabled


Terminal 54 Live Zero

(AN27)

Set to “1” Enabled


Jog Speed

(C20)

Set to “50” Hz


Frequency Command 2

(C30)

Set to “2” Analog Input 54


Terminal 27 Digital Input

(E03)

Set to “2” Coast inverse


Terminal 32 Digital Input

(E05)

Set to “14” Jog


Terminal 33 Digital Input

(E06)

Set to “6” Stop Inverse


Relay 1

(E24)

Set to “9” Alarm


Relay 2

(E24)

Set to “5” Running


Electronic Overload

(F10)

Set to “4” Elec OL Trip 1


Motor Thermistor Input

(F12)

Set to “0” None


Auto-Reset (Times)

(H04)

Set to “13” Infinite Auto Reset


Drive Programming


Loss of reference control – Run at preset speed

Main Menu

Parameter data set

Down arrow

AN - ##

OK