Table – 3 (575V)

Device

AF - 600 HP Rating(s)

Minimum Wire Size

Maximum Wire Size Required Torque

Load Reactor (6KFP

Series)

1 through 5

# 22 AWG

# 10 AWG

4.5 lb. in.

7.5 through 20

# 14 AWG

# 6 AWG

16 lb. in.

25 through 40

# 18 AWG

# 4 AWG

16 lb. in.

50 through 100

# 6 AWG

1/0

45 (6 - 4AWG), 50

(2-1/0 AWG)

125

# 2 AWG

4/0

150 lb. in.

150

Note 2

Note 2

Note 1

Load Reactor (6KFP*L

Series) - 3% Z

1 through 10

# 22 AWG

# 10 AWG

4.5 lb. in.

15 through 20

# 14 AWG

# 6 AWG

16 lb. in.

25

# 18 AWG

# 4 AWG

16 lb. in.

30 through 75

# 6 AWG

# 1/0

45 (6 - 4AWG), 50

(2-1/0 AWG)

100 through 650

Note 2

Note 2

Note 1

Load Reactor (6KFP*L

Series) - 1% Z

1 through 10

# 22 AWG

# 10 AWG

4.5 lb. in.

15 through 20

# 14 AWG

# 6 AWG

16 lb. in.

25

# 22 AWG

# 14 AWG

16 lb. in.

30

# 14 AWG

# 6 AWG

16 lb. in.

40 through 75

# 6 AWG

# 1/0

45 (6 - 4AWG), 50

(2-1/0 AWG)

100 through 650

Note 2

Note 2

Note 1

Control Terminal Board

2 through 300

# 26 AWG

# 10 AWG

Note 1

Note (1): For unmentioned torques, Refer UL508A tables in tab "UL508A" in the same excel file