1.7 Optional Components

1.7.1 Optional Unit Size 6x components

Units are manufactured in different configurations due to the optional com-
ponents available. Depending on the unit configuration, optional equipment
may be mounted in the inverter, rectifier or option cabinet. The table below
lists the components available and the cabinet where it is factory installed.

Optional Component

Cabinet Location

Mains Options

AC fuse

Rectifier or inverter

Disconnect

Option

A1 RFI filter

Option

Load share

Rectifier

1.8 Tools Required

Operating Instructions for the Drives Series Frequency Converter

Metric socket set

7–19 mm

Socket extensions

100 mm–150 mm (4 in and 6 in)

Torx driver set

T10 - T50

Torque wrench

0.675–19 Nm (6–170 in-lbs)

Needle nose pliers

Magnetic sockets

Ratchet

Hex wrench set

Screwdrivers

Standard and Philips

Additional Tools Recommended for Testing

Digital volt/ohmmeter (must be rated for 1200 VDC for 690 V units)
Analog voltmeter
Oscilloscope
Clamp-on style ammeter
Test cable p/n 6KAF6H8766
Signal test board p/n 6KAF6H8437
Power supply: 610 - 800 VDC, 250 mA to supply external power to 4
power cards and the control card.
Power supply : 24 VDC, 2 A for external 24 V power supply.

1.9 General Torque Tightening Values

For fastening hardware described in this manual, the torque values in the table below are used. These values are not intended for SCR, diode, or IGBT fasteners.
See the instructions included with those replacement parts for correct values.

Shaft Size

Driver Size Torx / Hex

Torque (in-lbs)

Torque (Nm)

M4

T-20 / 7 mm

10

1.0

M5

T-25 / 8 mm

20

2.3

M6

T-30 / 10 mm

35

4.0

M8

T-40 / 13 mm

85

10

M10

T-50 / 17 mm

170

19

M12

18 mm / 19 mm

170

19

Table 1.7: Torque Values Table