High power service manual for unit sizes 6x – GE Industrial Solutions AF-600 FP High Power Unit Sizes 6x User Manual

Page 58

Advertising
background image

ALARM 38, Internal fault:
Contact the local GE supplier.

0

Serial port cannot be restored. Serious hardware failure

256-258

Power EEPROM data is defect or too old

512

Control board EEPROM data is defect or too old

513

Communication time out reading EEPROM data

514

Communication time out reading EEPROM data

515

Application Orientated Control cannot recognize the EE-
PROM data

516

Cannot write to the EEPROM because a write command
is on progress

517

Write command is under time out

518

Failure in the EEPROM

519

Missing or invalid Barcode data in EEPROM

783

Parameter value outside of min/max limits

1024-1279 A can message that has to be sent, couldn't be sent

1281

Digital Signal Processor flash timeout

1282

Power micro software version mismatch

1283

Power EEPROM data version mismatch

1284

Cannot read Digital Signal Processor software version

1299

Option SW in slot A is too old

1300

Option SW in slot B is too old

1301

Option SW in slot C0 is too old

1302

Option SW in slot C1 is too old

1315

Option SW in slot A is not supported (not allowed)

1316

Option SW in slot B is not supported (not allowed)

1317

Option SW in slot C0 is not supported (not allowed)

1318

Option SW in slot C1 is not supported (not allowed)

1379

Option A did not respond when calculating Platform Ver-
sion.

1380

Option B did not respond when calculating Platform Ver-
sion.

1381

Option C0 did not respond when calculating Platform
Version.

1382

Option C1 did not respond when calculating Platform
Version.

1536

An exception in the Application Orientated Control is reg-
istered. Debug information written in Keypad

1792

DSP watchdog is active. Debugging of power part data
Motor Orientated Control data not transferred correctly

2049

Power data restarted

2064-2072 H081x: option in slot x has restarted
2080-2088 H082x: option in slot x has issued a powerup-wait
2096-2104 H083x: option in slot x has issued a legal powerup-wait

2304

Could not read any data from power EEPROM

2305

Missing SW version from power unit

2314

Missing power unit data from power unit

2315

Missing SW version from power unit

2316

Missing io_statepage from power unit

2324

Power card configuration is determined to be incorrect at
power up

2325

A power card has stopped communicating while main
power is applied

2326

Power card configuration is determined to be incorrect
after the delay for power cards to register

2327

Too many power card locations have been registered as
present

2330

Power size information between the power cards does
not match

2561

No communication from DSP to ATACD

2562

No communication from ATACD to DSP (state running)

2816

Stack overflow Control board module

2817

Scheduler slow tasks

2818

Fast tasks

2819

Parameter thread

2820

Keypad Stack overflow

2821

Serial port overflow

2822

USB port overflow

2836

cfListMempool to small

3072-5122 Parameter value is outside its limits

5123

Option in slot A: Hardware incompatible with Control
board hardware

5124

Option in slot B: Hardware incompatible with Control
board hardware

5125

Option in slot C0: Hardware incompatible with Control
board hardware

5126

Option in slot C1: Hardware incompatible with Control
board hardware

5376-6231 Out of memory

ALARM 39, Heatsink sensor
No feedback from the heatsink temperature sensor.
The signal from the IGBT thermal sensor is not available on the power card.
The problem could be on the power card, on the gate drive card, or the ribbon
cable between the power card and gate drive card.

WARNING 40, Overload of Digital Output Terminal 27
Check the load connected to terminal 27 or remove the short-circuit con-
nection. Check par. E-00 Digital I/O Mode and par. E-51 Terminal 27 Mode.

WARNING 41, Overload of Digital Output Terminal 29
Check the load connected to terminal 29 or remove the short-circuit con-
nection. Check par. E-00 Digital I/O Mode and par. E-52 Terminal 29 Mode

WARNING 42, Overload of Digital Output on X30/6 or Overload of Digital
Output on X30/7
For X30/6, check the load connected to X30/6 or remove the short-circuit
connection. Check par. E-56 Term X30/6 Digi Out (OPCGPIO)(OPCGPIO General
Purpose I/O Option Module).
For X30/7, check the load connected to X30/7 or remove the short-circuit
connection. Check par. E-57 Term X30/7 Digi Out (OPCGPIO) (OPCGPIO General
Purpose I/O Option Module).

ALARM 46, Power card supply
The supply on the power card is out of range.
There are three power supplies generated by the switch mode power supply
(SMPS) on the power card: 24 V, 5V, +/- 18V. When powered with 24 VDC with
the OPC24VPS 24 V DC External Supply Module option, only the 24 V and 5 V
supplies are monitored. When powered with three phase mains voltage, all
three supplied are monitored.

WARNING 47, 24 V supply low:
The external 24 V DC backup power supply may be overloaded, otherwise
contact the local GE supplier.

WARNING 48, 1.8 V supply low:
The 1.8 Volt DC supply used on the control card is outside of allowable limits.
The power supply is measured on the control card.

ALARM 49, Speed Limit:
When the speed is not within the specified range in par. F-18 Motor Speed
Low Limit [RPM]
and par. F-17 Motor Speed High Limit [RPM] the drive will
show a warning. When the speed is below the specified limit in par. H-36 Trip
Speed Low [RPM]
(except when starting or stopping) the drive will trip.

ALARM 50, Auto Tune calibration failed:
Contact the local GE supplier.

ALARM 51, Auto Tune check Unom and Inom:
The setting of motor voltage, motor current, and motor power is presumably
wrong. Check the settings.

ALARM 52, Auto Tune low Inom:
The motor current is too low. Check the settings.

ALARM 53, Auto Tune motor too big:
The motor is too big for the Auto Tune to be carried out.

High Power Service Manual for Unit Sizes 6x

57