High power service manual for unit sizes 6x – GE Industrial Solutions AF-600 FP High Power Unit Sizes 6x User Manual

Page 52

Advertising
background image

No.

Description

Warning

Alarm/Trip

Alarm/Trip Lock

Parameter Reference

1

10 Volts low

X

2

Live zero error

(X)

(X)

AN-01

3

No motor

(X)

H-80

4

Mains phase loss

(X)

(X)

(X)

SP-12

5

DC link voltage high

X

6

DC link voltage low

X

7

DC over voltage

X

X

8

DC under voltage

X

X

9

Inverter overloaded

X

X

10

Motor Electronic Thermal Overload over temperature

(X)

(X)

F-10

11

Motor thermistor over temperature

(X)

(X)

F-10

12

Torque limit

X

X

13

Over Current

X

X

X

14

Earth fault

X

X

X

15

Hardware mismatch

X

X

16

Short Circuit

X

X

17

Control word timeout

(X)

(X)

O-04

22

Hoist mechanical brake

X

23

Internal fans

X

B-2#

24

External fans

X

SP-53

25

Brake resistor short-circuited

X

26

Brake resistor power limit

(X)

(X)

B-13

27

Brake chopper short-circuited

X

X

28

Brake check

(X)

(X)

B-15

29

Heatsink temp

X

X

X

30

Motor phase U missing

(X)

(X)

(X)

H-78

31

Motor phase V missing

(X)

(X)

(X)

H-78

32

Motor phase W missing

(X)

(X)

(X)

H-78

33

Inrush fault

X

X

34

Network communication fault

X

X

36

Mains failure

X

X

37

Phase imbalance

X

38

Internal fault

X

X

39

Heatsink sensor

X

X

40

Overload of Digital Output Terminal 27

(X)

E-00 & E-51

41

Overload of Digital Output Terminal 29

(X)

E-00 & E-52

42

Overload of Digital Output on X30/6 or Overload of Digital
Output on X30/7

(X)

E-56 & E-57

45

Earth fault 2

X

X

X

46

Power card supply

X

X

47

24 V supply low

X

X

X

48

1.8 V supply low

X

X

49

Speed limit

X

X

50

Auto Tune calibration failed

X

51

Auto Tune check U

nom

and I

nom

X

52

Auto Tune low I

nom

X

53

Auto Tune motor too big

X

54

Auto Tune motor too small

X

55

Auto Tune parameter out of range

X

56

Auto Tune interrupted by user

X

57

Auto Tune timeout

X

58

Auto Tune internal fault

X

X

59

Current limit

X

60

External interlock

X

X

61

Tracking Error

(X)

(X)

H-20

62

Output Frequency at Maximum Limit

X

63

Mechanical brake low

(X)

B-20

Table 4.2: Alarm/Warning code list

High Power Service Manual for Unit Sizes 6x

51

4

Advertising