5.2.3 Current Sensor Faults

When a current sensor fails, it is indicated sometimes by an overcurrent alarm that cannot be reset, even with the motor leads disconnected. Most often, however,
the frequency converter will experience frequent false earth fault trips. This is due to the DC offset failure mode of the sensors.

To explain this it is necessary to investigate the internal makeup of a Hall effect type current sensor. Included inside the device is an op-amp to amplify the signal
to usable levels in the receiving circuitry. Like any op-amp, the output at zero input level (zero current flow being measured) should be zero volts, exactly halfway
between the plus and minus power supply voltages. A tolerance of +/- 15mv is acceptable. In a three phase system that is operating correctly, the sum of the
three output currents should always be zero.

When the sensor becomes defective, the output voltage level varies by more than the 15mv allowed. The defective current sensor in that phase indicates current
flow when there is none. This results in the sum of the three output currents being a value other than zero, an indication of leakage current flowing. If the deviation
from zero (current amplitude) approaches a specific level, the frequency converter assumes an earth fault and issues an alarm.

The simplest method of determining whether a current sensor is defective is to disconnect the motor from the frequency converter, then observe the current in
the frequency converter display. With the motor disconnected, the current should be zero. A frequency converter with a defective current sensor will indicate
some current flow. An indication of a fraction of an amp is tolerable. However, that value should be considerably less than one amp. If the display shows more
than one amp of current, there is a defective current sensor.

To determine which current sensor is defective, measure the voltage offset at zero current for each current sensor. See the current sensor test procedure.

Check also that all current scaling cards are properly connected to the MDCIC boards. An incorrect or improperly connected scaling card can result in an incorrect
current measurement. If a current scaling card is missing, the drive will trip on overcurrent or earth fault.

5.3 Electromagnetic Interference

5.3.1 Effect of EMI

The following is an overview of general signal and power wiring considerations when addressing the Electromagnetic Compatibility (EMC) concerns for typical
commercial and industrial equipment. High-frequency RF emissions and immunity are discussed. Compliance to national and European CE EMC directives are
required.

While electromagnetic interference (EMI) related disturbances to frequency
converter operation are uncommon, the following detrimental EMI effects
may be seen:

Motor speed fluctuations

Serial communication transmission errors

Drive CPU exception faults

Unexplained frequency converter trips

A disturbance resulting from other nearby equipment is more common. Generally, other industrial control equipment has a high level of EMI immunity. However,
non-industrial, commercial, and consumer equipment is often susceptible to lower levels of EMI. Detrimental effects to these systems may include the following:

Pressure/flow/temperature signal transmitter signal distortion or aberrant behaviour

Radio and TV interference

Telephone interference

Computer network data loss

Digital control system faults

High Power Service Manual for Unit Sizes 6x