High power service manual for unit sizes 6x – GE Industrial Solutions AF-600 FP High Power Unit Sizes 6x User Manual

Page 133

Advertising
background image

Pin No. Schematic

Acronym

Function

Description

Reading Using a Digital Voltmeter

18

HI_LOW

Control signal from
Power Card

Signal to switch fan speeds between high and low

+5VDC = fans on high,
Otherwise, 0VDC.

19

SCR_DIS

Control signal for SCR
front end

Indicates SCR front end is enabled or disabled.

0.6 to 0.8 VDC – SCRs enabled
0VDC – SCR disabled

20

INV_DIS

Control signal from
Power Card

Disables IGBT gate voltages

5VDC – inverter disabled
0VDC – inverter enabled

21

Not

used

22

UINVEX

Bus Voltage scaled
down

Signal proportional to UDC

OV switch must be off
- 1 VDC = 450 VDC [T4/T5]
- 1 VDC = 610 VDC [T7]

23

VDD

+24 VDC power supply

Yellow LED indicates voltage is present.

+24 VDC regulated supply
+23 to 25 VDC

24

VCC

+5.0 VDC regulated sup-
ply. +4.75-5.25 VDC

The green LED indicates voltage is present.

+5.0 VDC regulated supply +4.75 to 5.25 VDC

25

GUP_T

IGBT gate signal, buf-
fered, U phase, positive.
Signal originates on
Control Card.

2v/div 100us/div Run

@10Hz

2.2–2.5 VDC
Equal on all phases
TP25-TP30

26

GUN_T

IGBT gate signal, buf-
fered, U phase, negative.
Signal originates on
Control Card.

2v/div 100us/div Run

@10Hz

2.2–2.5 VDC
Equal on all phases
TP25-TP30

27

GVP_T

IGBT gate signal, buf-
fered, V phase, positive.
Signal originates on
Control Card.

2v/div 100us/div Run

@10Hz

2.2–2.5 VDC
Equal on all phases
TP25-TP30

28

GVN_T

IGBT gate signal, buf-
fered, V phase, negative.
Signal originates on
Control Card.

2v/div 100us/div Run

@10Hz

2.2–2.5 VDC
Equal on all phases
TP25-TP30

29

GWP_T

IGBT gate signal, buf-
fered, W phase, positive.
Signal originates on
Control Card.

2v/div 100us/div Run

@10Hz

2.2–2.5 VDC
Equal on all phases
TP25-TP30

30

GWN_T

IGBT gate signal, buf-
fered, W phase, nega-
tive. Signal originates on
Control Card.

2v/div 100us/div Run

@10Hz

2.2–2.5 VDC
Equal on all phases TP25-TP30

High Power Service Manual for Unit Sizes 6x

132

10

Advertising