4 electrostatic discharge (esd), 5 unit size definitions, 6 ratings tables – GE Industrial Solutions AF-600 FP High Power Unit Sizes 6x User Manual

Page 7: High power service manual for unit sizes 6x

Advertising
background image

1.

Disconnect mains prior to inspection or making repairs.

2.

DO NOT touch electrical parts of frequency converter when connected to mains. After removing power from mains, wait 40 minutes before touching
any electrical parts. See the label on the front of the frequency converter door for specific discharge time.

3.

The STOP key on the keypad does not disconnect mains.

4.

During operation and while programming parameters, the motor may start without warning. Activate the STOP key when changing data.

1.4 Electrostatic Discharge (ESD)

When performing service, use proper ESD procedures to prevent damage to sensitive components.

Many electronic components within the frequency converter are sensitive to static electricity. Voltages so low that they cannot be felt, seen or heard can reduce
the life, affect performance, or completely destroy sensitive electronic components.

1.5 Unit Size Definitions

AF-600 FP 380-480 VAC Power

kW

@400 VAC

HP

@460 VAC

Unit Size

500

650

61 / 63

560

750

61 / 63

630

900

62 / 64

710

1000

62 / 64

800

1200

62 / 64

1000

1350

62 / 64

Table 1.1: AF-600 FP 380-480 VAC

AF-650 GP 380-480 VAC Power

kW

@400 VAC

HP

@460 VAC

Unit Size

450/ 500

600/ 650

61 / 63

500 / 560

650 / 750

61 / 63

560/ 630

750 / 900

62 / 64

630 / 710

900 / 1000

62 / 64

710 / 800

1000 / 1200

62 / 64

800 / 1000

1200 / 1350

62 / 64

Table 1.2: AF-650 GP 380-480 VAC

AF-600 FP 525-690 VAC Power

kW

@550 VAC

HP

@575 VAC

kW

@690 VAC

Unit Size

560

750

710

61 / 63

670

950

800

61 / 63

750

1050

900

61 / 63

950

1150

1000

62 / 64

1000

1350

1200

62 / 64

1100

1550

1400

62 / 64

Table 1.3: AF-600 FP 525-690 VAC

AF-650 GP 525-690 VAC Power

kW

@550 VAC

HP

@575 VAC

kW

@690 VAC

Frame Size

500 / 560

650 / 750

630 / 710

61 / 63

560 / 670

750 / 950

710 / 800

61 / 63

670 / 750

950 / 1050

800 / 900

61 / 63

750 / 850

1050 / 1150

900 / 1000

62 / 64

850 / 1000

1150 / 1350

1000 / 1200

62 / 64

1000 / 1100

1350 / 1550

1200 / 1400

62 / 64

Table 1.4: AF-650 GP 525-690 VAC

1.6 Ratings Tables

DC Voltage Levels

380-480V &

380-500V units

525-690V units

Inrush Circuit Enabled

370

550

Inrush Circuit Disabled

395

570

Inverter Undervoltage Disable

373

553

Undervoltage Warning

410

585

Inverter Undervoltage Re-Enable (warning reset)

413

602

Overvoltage Warning (w/o Brake)

817

1084

Dynamic Brake Turn-on

810

1099

Inverter Overvoltage Re-Enable (warning reset)

821

1099

Overvoltage Warning (with Brake)

828

1109

Overvoltage Trip

855

1130

High Power Service Manual for Unit Sizes 6x

6

1