7.2 Instructions

7.2.1 AC Line Input Fuses

AC Fuse Location
AC line fuses are optional. AC fuses are located in the rectifier cabinet if they are the only power option added to the frequency converter. If additional power
options are present, the AC fuses will be located in the options cabinet.

AC Fuses Located in the Rectifier Cabinet

1.

Remove bottom safety cover from rectifier cabinet.
Note: Fuses must be removed sequentially, front to back. If only the fuse located in the back needs to be replaced, remove front and middle fuses to
gain access to the back fuse. If additional access is necessary, the left-most inverter module can be removed from the inverter cabinet. Refer to inverter
removal instructions.

2.

Remove bolts (8mm) securing fuses in place.

AC Fuses Located in Options Cabinet

1.

Remove covers from options cabinet to access fuses.

2.

Remove bolts (8mm) securing fuses in place.

1

2

3

4

5

AC Fuses Located in the Rectifier Cabinet

1

Rectifier module

4

Middle AC fuse mounting bracket (S)

2

AC mains input fuse

5

Front AC fuse mounting bracket (R)

3

Back AC fuse mounting bracket (T)

High Power Service Manual for Unit Sizes 6x

99

7