High power service manual for unit sizes 6x – GE Industrial Solutions AF-600 FP High Power Unit Sizes 6x User Manual

Page 9

Advertising
background image

Mains supply 3 x 525 - 690 V

Model number

AF-600 FP

750

950

1050

1150

1350

1550

AF-650

GP

900

1000

1150

1250

1350

1550

Light duty (LD) current ratings (110 %):

Output current

Nominal [A] (525-550 V)

763

889

988

1108

1317

1479

MAX (60 sec) [A] (525-550 V)

839

978

1087

1219

1449

1627

Nominal [A] (551-690 V)

730

850

945

1060

1260

1415

MAX (60 sec) [A] (551-690 V)

803

935

1040

1166

1386

1557

Output

Nominal [kVA] (550 V)

727

847

941

1056

1255

1409

Nominal [kVA] (575 V)

727

847

941

1056

1255

1409

Nominal [kVA] (690 V)

872

1016

1129

1267

1506

1691

Typical shaft output

[kW] (550 V)

560

670

750

850

1000

1100

[HP] (575 V)

750

950

1050

1150

1350

1550

[kW] (690 V)

710

800

900

1000

1200

1400

Heavy duty (HD) torque (160 %):

Output current

Nominal [A] (525-550 V)

659

763

889

988

1108

1317

MAX (60 sec) [A] (525-550 V)

989

1145

1334

1482

1662

1976

Nominal [A] (551-690 V)

630

730

850

945

1060

1260

MAX (60 sec) [A] (551-690 V)

945

1095

1275

1418

1590

1890

Output

Nominal [kVA] (550 V)

628

727

847

941

1056

1255

Nominal [kVA] (575 V)

627

727

847

941

1056

1255

Nominal [kVA] (690 V)

753

872

1016

1129

1267

1506

Typical shaft output

[kW] (550 V)

500

560

670

750

850

1000

[HP] (575 V)

650

750

950

1050

1150

1350

[kW] (690 V)

630

710

800

900

1000

1200

600V Power loss Light
duty (LD) [W]

8933

10310

11692

12909

15358

17602

600V Power loss Heavy
duty (HD) [W]

7586

8683

10298

11329

12570

15258

690V Power loss Light
duty (LD) [W]

9212

10659

12080

13305

15865

18173

690V Power loss Heavy
duty (HD) [W]

7826

8983

10646

11681

12997

15763

Limits and Ranges

Overcurrent Warning

A rms Out

1648

1977

2336

2471

2965

3505

Overcurrent Alarm (1.5
sec delay)

A rms Out

1648

1977

2336

2471

2965

3505

Earth (Ground) Fault
Alarm

A rms Out

330

382

445

494

554

659

Short Curcuit Alarm

A rms Out

2094

2510

2980

3140

3766

4470

Heatsink Over Temper-

ature

° C

95

105

95

95

105

95

Heatsink Under Tem-

perature Warning

° C

0

0

0

0

0

0

Power Card Ambient

Over Temperature

° C

68

68

68

68

68

68

Power Card Ambient

Under Temperature

° C

-20

-20

-20

-20

-20

-20

Mains Phase Warning (5
sec delay)

DC Bus Ripple Vpeak

50

50

50

50

50

50

Mains Phase Alarm (25
sec delay)

DC Bus Ripple Vpeak

50

50

50

50

50

50

Table 1.6: Mains supply 3 x 525 - 690 V