CPS3200U Upstream System – 23” Product Manual

CPS3200U

CC848779826 r09 December 2013

11

connections are 60Vdc and 0.5 amperes. Exceeding these maximum ratings could result in fire or damage to the

unit.

• Fuse and/or circuit breaker loads must not exceed 80% of the fuse and/or circuit breaker current rating.

Distribute loads across the panel.

• The short circuit current capability of the battery input to the panel must not exceed 10,000A.
• DC branch circuits to this equipment must be protected with either fuses or circuit breakers. Refer to the

equipment ratings to assure rating of equipment will not exceed 80% of the value of the protector chosen.

• For applications in cabinets, huts, vaults, and central offices, the CPS3200U mounting framework must be

connected to the system integrated ground grid.

• Installing fuses or circuit breakers not specified for use in these modules may result in injury to service personnel

or equipment damage. Use only replacement parts listed in this manual and on the equipment drawings.

• The telecom-type (e.g., GMT type) fuses can produce sparks during interruption or clearing of a fault on a high

energy circuit. Use only fuses provided with safety caps for this type of circuit. Installing telecom-type fuses not

equipped with safety caps may result in injury to service personnel.

• The designed capacitance between +/-190V RFT-V conductors is 2.2uF and the measured capacitance between

+/-190V and earth is 4.4uF. DO NOT add capacitance to the system to reach values that exceed safety limits per

the following figure: