Apply DC Power

Apply DC power by turning on input fuses or circuit breakers. Power the fan shelf and the converter shelf

simultaneously. The system will operate from voltages between -40 and -60 volts with normal status at feed voltages

between -52 Volts and -54.5 Volts.
Fault LEDs will flash red until communications is established between the alarm card and each converter. The alarm

card will flash its fault LED until connection is confirmed to the QS941, if present. If no QS941 is present the alarm cards

will flash their red LED until they are set to address 0, 0 as described in the Set Shelf ID and Attach Alarm Wiring

section.
Complete UL 60950-21 step 7 under Inspect the Network to test each circuit after DC power is applied.

Recognizing Normal States

Once power is provided to the CPS3200U system the LEDs on the converters will illuminate. Understanding what the

LEDs mean allows one to recognize normal states and diagnose abnormal states.

Step

Action

1.

Observe the LEDs.

2.

Use the state table below to determine the state of the system and required corrective actions

if needed.

Figure 27 QS982A Faceplate and LEDs

(Note: Test points work best if each voltage is measured with respect to ground)