CPS3200U Upstream System – 23” Product Manual

CPS3200U

CC848779826 r09 December 2013

48

Table 8 Alarm Reference

QS941

Alarm Card

Converter Card

Alarm Display

What it means

LED

State

Relay

State

Alarm

LED

State

Relay

State

OK

LED

State

Alarm

LED

State

Corrective Action

Input Power

B1-8 Power Fail

Yellow

Min

B Red

Min

Green

Off

Reconnect DC input

power flowing to the

B1-8 input terminal

Input Power

A9-16 Power Fail Yellow

Min

A Red

Min

Green

Off

Reconnect DC input

power flowing to the

A9-16 input terminal

Input Power

B9-16 Power Fail Yellow

Min

B Red

Min

Green

Off

Reconnect DC input

power flowing to the

B9-16 input terminal.

Input Power

Mul Circuit Fail

A1-8 & B1-8

Power Fail

Red

Maj

A Red

B Red

Maj

Green

Off

Reconnect DC input

power flowing to the

A1-8 input terminal

and Reconnect DC

input power flowing to

the B1-8 input

terminal

Input Power

Mul Circuit Fail

A9-16 & B9-16

Power Fail

Red

Maj

A Red

B Red

Maj

Green

Off

Reconnect DC input

power flowing to the

A9-16 input terminal.

Reconnect DC input

power flowing to the

B9-16 input terminal.

Load Drop

Load Drop

Yellow

Min

A, B &

OK

Green

Green

Off

Check the integrity of

the circuits going to

the load. Or Adjust

load drop threshold to

0 to disable this

feature.

Load Share

As set of circuits

assigned to one

remote

destination are

not sharing

current as would

be expected

Yellow

Min

A, B &

OK

Green

Green

Off

Check the integrity of

the circuits going to

the load. Or Adjust

load share threshold

to disable this feature.

Line Test

OK, Fail or

Aborted

A, B &

OK

Green

Green

Off

Estimated line

resistance has

increased since last

measurement.

Loss Of

Redundancy

Yellow

Min

A, B &

OK

Green

Green

Off

The loss of n additional

circuits will cause

customers to lose

service. Check

redundancy threshold

in the configuration.