Appendix b: alarm reference table, Table 8 alarm reference – GE Industrial Solutions CPS3200U User Manual

Page 47

Advertising
background image

CPS3200U Upstream System – 23” Product Manual

CPS3200U

CC848779826 r09 December 2013

47

Appendix B: Alarm Reference Table

This Alarm Table shows how FTTN Alarms are categorized by the QS941 Controller. Details of non-FTTN Alarms can be

found in the Plant Level product manuals. Many alarms are best processed at the converter shelf alarm card and

converter card level.

Table 8 Alarm Reference

QS941

Alarm Card

Converter Card

Alarm Display

What it means

LED

State

Relay

State

Alarm

LED

State

Relay

State

OK

LED

State

Alarm

LED

State

Corrective Action

Circuit Fail

Short + to -

Yellow

Min

Yellow

Min

Green

Flashing

Yellow

Make sure each

converter has an

independent isolated

send and return path.

Circuit Fail

Short to Ground

Yellow

Min

Yellow

Min

Flashing

Red

Flashing

Red

Make sure each

converter has an

independent isolated

send and return path.

Communication

Fail

1 Card Removed Yellow

Min

Yellow

Min

Green

Off

Check to see that all

cards are seated.

Replace non-

functioning cards.

Communication

Fail

2 Cards

Removed

Red

Maj

Check to see that all

cards are seated.

Replace non-

functioning cards.

Communication

Fail

Communication

Cable Removed

Red

Maj

Flashing

Red

Green

Off

Check communication

path from alarm cards

to QS941 controller. If

no controller is

present, set alarm

card rotary switch to

position 0 for contact

closures only

communication.

Communication

Fail

Alarm Card

Removed

Red

Maj

Green

Flashing

Red

Replace Alarm card.

None

Standby

Green

Green

Yellow

Remove unit from

standby if desired

using QS941 or

Ethernet interface

Circuit Fail

Open Fuse

Yellow

Min

Yellow

Min

Green

Flashing

Yellow

Replace unit. Note:

Restoring service to

one line will interrupt

service to the other

line served by that

card.

Circuit Fail

Under Voltage

Yellow

Min

Yellow

Min

Flashing

Yellow

Replace unit. Note:

Restoring service to

one line will interrupt

service to the other

line served by that

card.

Fan Fail

1 Fan Tray Failed Yellow

Min

Yellow

Min

Green

Off

Replace fan tray.

Fan Fail

1 of 6 fans Failed

on one Fan Tray

Yellow

Min

Yellow

Min

Green

Off

Replace fan tray.

Fan Fail

2 Fan Trays

Failed

Red

Maj

Red

Maj

Green

Off

Replace fan trays.

Input Power

A1-8 Power Fail

Yellow

Min

A Red

Min

Green

Off

Reconnect DC input

power flowing to the

A1-8 input terminal.

Advertising