Figure 40 output connectors, Table 7 output connector pinout – GE Industrial Solutions CPS3200U User Manual

Page 41

Advertising
background image

CPS3200U Upstream System – 23” Product Manual

CPS3200U

CC848779826 r09 December 2013

41

Figure 40 Output Connectors

Wireset Connector: RJ-21 type 50 pin plug:

• 22 AWG solid or stranded AMP 552173-1 or equivalent.
• 24 AWG solid or stranded or 26 AWG solid AMP 229974-1 or equivalent.
• The connector shall be arranged with a right angle housing such that the cable exits to the pin 1 side.

Table 7 Output Connector Pinout

Connector for Circuits 1-8 (Shelf J1)

Connector for Circuits 9-16 (Shelf J2)

Conv Out Pos Color

Conv Out Pos Color

Conv Out Pos Color

Conv Out Pos Color

1a-

1 BL / W

1a+

26 W / BL

9a-

1 BL / W

9a+

26 W / BL

1b-

2 O / W

1b+

27 W / O

9b-

2 O / W

9b+

27 W / O

2a-

3 G / W

2a+

28 W / G

10a-

3 G / W

10a+

28 W / G

2b-

4 BR / W

2b+

29 W / BR

10b-

4 BR / W

10b+

29 W / BR

3a-

5 SL / W

3a+

30 W / SL

11a-

5 SL / W

11a+

30 W / SL

3b-

6 BL / R

3b+

31 R / BL

11b-

6 BL / R

11b+

31 R / BL

4a-

7 O / R

4a+

32 R / O

12a-

7 O / R

12a+

32 R / O

4b-

8 G / R

4b+

33 R / G

12b-

8 G / R

12b+

33 R / G

5a-

9 BR / R

5a+

34 R / BR

13a-

9 BR / R

13a+

34 R / BR

5b-

10 SL / R

5b+

35 R / SL

13b-

10 SL / R

13b+

35 R / SL

6a-

11 BL / BK

6a+

36 BK / BL

14a-

11 BL / BK

14a+

36 BK / BL

6b-

12 O / BK

6b+

37 BK / O

14b-

12 O / BK

14b+

37 BK / O

7a-

13 G / BK

7a+

38 BK / G

15a-

13 G / BK

15a+

38 BK / G

7b-

14 BR / BK

7b+

39 BK / BR

15b-

14 BR / BK

15b+

39 BK / BR

8a-

15 SL / BK

8a+

40 BK / SL

16a-

15 SL / BK

16a+

40 BK / SL

8b-

16 BL / Y

8b+

41 Y / BL

16b-

16 BL / Y

16b+

41 Y / BL

spare

17 O / Y

spare

42 Y / O

spare

17 O / Y

spare

42 Y / O

spare

18 G / Y

spare

43 Y / G

spare

18 G / Y

spare

43 Y / G

spare

19 BR / Y

spare

44 Y / BR

spare

19 BR / Y

spare

44 Y / BR

spare

20 SL / Y

spare

45 Y / SL

spare

20 SL / Y

spare

45 Y / SL

spare

21 BL / V

spare

46 V / BL

spare

21 BL / V

spare

46 V / BL

spare

22 O / V

spare

47 V / O

spare

22 O / V

spare

47 V / O

spare

23 G / V

spare

48 V / G

spare

23 G / V

spare

48 V / G

spare

24 BR / V

spare

49 V / BR

spare

24 BR / V

spare

49 V / BR

*FR GRD

25 SL / V

*FR GRD

50 V / SL

*FR GRD

25 SL / V

*FR GRD

50 V / SL

*EMI performance is enhanced when the output cable shield is grounded only at the CPS3200 end of the shield.