9 reference information, Qs982a converter led information map, Figure 36 qs982 leds and test points – GE Industrial Solutions CPS3200U User Manual
Page 37: Table 5 qs982a converter led information map, Overview
CPS3200U Upstream System – 23” Product Manual
CPS3200U
CC848779826 r09 December 2013
37
9 Reference Information
Overview
This section contains additional information (connector pin designations, etc.) that may be required for making,
customizing, or troubleshooting system connections.
QS982A Converter LED Information Map
Figure 36 QS982 LEDs and Test Points
Table 5 QS982A Converter LED Information Map
Action Required
OK LED
Fault LED
Conditions
Notes
None
Green
Off
All OK
Verify circuit
configuration
Off
Yellow
Standby
Standby can be set using the QS941
controller display or remotely using a
web browser.
Check seating on
Alarm card and
converter card
Green
Blink Red On ½ second,
Off ¼ second
Loss of comm.
Check 5 pin
protectors and faults
to ground
Red Blink
Red Blink
Ground fault
Check output lines for
shorts to each other
Green
Yellow Blink
Overcurrent or under
voltage
Replace unit
Red Blink
Off
OV or internal failure
Solve Thermal
problem
Off
Red Blink
Thermal Alarm
Latch off after 3 retry cycles
Check source voltage Off
Off
card not powered or
input fuse failure
Observe Lamp Test
Bi-Color: 4.5 seconds
on, 4.5 seconds on and
1 second off
Bi-Color: 4.5 seconds
on, 4.5 seconds on and
1 second off
Lamps test requested
from controller