Specifications

Table 1 Specifications

Electrical

Parameter

Symbol

Min

Typical

Max

2

Unit

Input Voltage

Operating Continuous

Non-operating, No Damage

V

I

-40

0

-52.8

-60

-40

Vdc

Transient (@ duration =)

5 Seconds

10 ms (

rise and fall rate of 10V/ms)

10 µs

1 µs

V

tr

V

tr

V

tr

V

tr

-65

-75

-100

-200

Vdc

Input Current - (per half shelf

at 97.7W on all circuits)

V

IN

= 54.4V

I

IN

34.7

Adc

V

IN

= 52.1V

I

IN

36.2

Adc

V

IN

= 42.6V

I

IN

44.3

Adc

V

IN

= 40.0V

I

IN

47.2

Adc

Temperature

Normal Operating Ambient

Temperature at 150 lfm airflow

T

A

-40

50

°C

Operating Ambient Temperature

at higher (TBD) airflow

T

A

-40

75

°C

Cold Start Temperature

T

A

-40

°C

Storage Temperature

T

stg

-55

85

°C

Power – per C/L Card

Input Power at -42.6 Vdc input

Pin

240

3

W

Power Dissipation

Pdiss

21

40*

W

Output Power

Pout

200

W

Output

Voltage – line to line

V

O

378

380

382

Vdc

Power – per C/L circuit

P

O

95.0

97.7

100

W

Current – per C/L circuit

I

OUT

251

257

262

mA

Isolation

Input to Output Voltage

1500

Vdc

Physical

Height

in (mm)

Width

in (mm)

Depth

in (mm)

Weight

lb (kg)

23-Inch Shelf

3.5 (88.9)

21.4 (543.6)

12 (304)

30 (13.6)

Fan Shelf

3.5 (88.9)

21.4 (543.6)

12 (304)

20 (9.0)

1U Baffle

1.75 (44.4)

21.4 (543.6)

12 (304)

4 (1.8)

Installation Category

CPS3200U output circuits are suitable for connection to telephone lines that are equipped with primary lightning

protectors consistent with UL 497. The user must provide protection on each copper pair to a level corresponding to a

CommScope 3C*EW Gas tube primary protector or equivalent gas tube protector [For example: 3C3EW provides the

part in a red color]. This protector has a voltage breakdown range of 265-465 Volts and an impulse spark over range of

<265-700 Volts. The 5-Pin protector must be marked as a “special circuit” consistent with the marking protocol in the

users network. Protectors are provided by the telco customer.

Network equipment and components along the powering circuit shall have suitable insulation resistance at 200 Vdc

from each conductor to ground and a total insulation resistance suitable for 400 Vdc from line to line.

2

Max = Absolute Maximum Rating

3

These are maximum situations with each circuit loaded to 100W. No actual or engineered application would load

every circuit to this level. In the absence of detailed information about the network we would recommend using the

typical dissipation value of 21 Watts for most applications with 30W per card for highly loaded networks.