Operating Manual LP 33U Series 10 & 20 kVA / S1

6.3.3 Messages list

Code

Message

Meaning

4111

RECTIFIER UTILITY OK

Rectifier input utility is again within the acceptable
tolerance (voltage, frequency and phase).

4114

UPS SHUTDOWN

(LOW BATTERY VOLTAGE)

The UPS is in Load OFF status, resulting in Battery supply
for the power supply.
Should the Battery voltage decrease to a value below of
the one set in a parameter, then power supply will
shutdown to avoid damage to the Battery

4119

BATTERY TEST STARTED

Start of manual or automatic battery test.
Rectifier output voltage is decreased to the value defined
by respective parameter.

4120

BATTERY TEST STOPPED

End battery test.
End of manual or automatic battery test.
Rectifier output voltage is restored to floating voltage.

4141

ISMAX DETECTION RECTIFIER

Detection of persistent booster (Is) current limitation.

4161

RECTIFIER ON

Rectifier received the command to switch ON.

4162

RECTIFIER OFF

Rectifier received the command to switch OFF for:
input utility out of tolerance / EPO / DC-Voltage max.

4163

GENERATOR ON

Customer Interface (X1 / 11, 22) received a Gen set ON
signaling. Operating mode dependent on setting of
respective parameters.

4164

GENERATOR OFF

Customer Interface (X1 / 11, 22) received a Gen set OFF
signaling. Function bypass enabled dependent on setting
of respective parameter.

4302

INVERTER CANNOT BE

TURNED ON

Inverter cannot be switched on because one of the
following conditions are still present:

-

Over temperature

-

Low battery voltage

-

Inverter fuses

-

Overload

-

K7 opening failure

-

High battery voltage

-

DC low

-

EPO (Emergency Power Off)

4303

INVERTER CANNOT BE

TURNED OFF

Inverter cannot be switched OFF, because the load cannot
be transferred on utility (voltage out of tolerance, not
synchronizing, bypass blocked).

4361

INVERTER ON

The command to start the inverter has been activated on
the control panel.

4362

INVERTER OFF

The command to switch OFF the inverter has been done by
the control panel or automatically for alarm detection.

4411

BYPASS UTILITY OK

Bypass input utility is again within the admitted tolerance
(Voltage, frequency and phase).

4500

COMMAND TOTAL OFF

Disconnection of the load by opening K4, K6 and K7 for:
EPO / Total Off / Overload / Stop operation.

4521

NO BYPASS POWER

With the load supplied by electronic bypass, a utility failure
or K6 opening occurred.

4534

MULTIPLE LOAD TRANSFER

2 transfers inverter-utility have been detected in a short
time, defined by respective parameter (default 30 seconds).