Operating Manual LP 33U Series 10 & 20 kVA / S1

Code

Message

Meaning

4535

BYPASS LOCKED

Transfer on utility not enabled due to settings of respective
parameters. Contactor K6 is open.

4536

BYPASS FREE

Settings of respective parameters enable bypass transfer
on utility. Contactor K6 can be closed.

4561

TOTAL OFF

Key Total Off behind the front door has been pressed, with
the output circuit breaker Q1 closed.

4562

DETOUR ON

The auxiliary contact indicates that manual bypass Q2 has
been closed.

4564

DETOUR OFF

The auxiliary contact indicates that manual bypass Q2 has
been opened.

4567

COMMAND LOAD ON UTILITY

The control unit received a command to transfer the load
on utility.

4568 COMMAND LOAD ON INVERTER The control unit received a command to transfer the load

on inverter.

4572

NO MORE OVERLOAD

End of the overload condition previously detected with
alarm 4570.

4580

INVERTER AND UTILITY

SYNCHRONIZED

The voltages of inverter and utility bypass are
synchronized.

4582

COMMAND NOT

TO SYNCHRONIZE

Command not to synchronize with utility has been done for:
utility bypass out of tolerance (alarm 4410) or setting
respective parameters.

4583

COMMAND TO SYNCHRONIZE

Command to synchronize with utility has been done for:
utility BP OK (4410) or setting respective parameters.

4600

COMMAND UPS ON

The ECO Mode function has been disabled or the
programmed time is expired.
The UPS returns to VFI mode supplying the load normally
by inverter.

4601

COMMAND UPS STANDBY

The function ECO Mode is enabled, and according to the
time program the UPS will run in ECO Mode, supplying the
load normally by utility.

4602

Q1 OPEN

The auxiliary contact indicates that the output switch Q1
has been opened.

4603

Q1 CLOSED

The auxiliary contact indicates that the output switch Q1
has been closed.

4699

BATTERY TEST IMPOSSIBLE

Not possible to start battery test (it is postponed) for:

-

No utility rectifier or bypass

-

Battery not fully charged

-

Load is below 10% or above 80%

4763

REMOTE CONTROL ON

Inverter can be started or shutdown by remote control.
Commands source can be chosen depending on the value
of respective parameter (password required):
0 = Only local panel
1 = Only Remote Control
2 = Both

4764

REMOTE CONTROL OFF

Inverter can be started or shutdown by remote control.
Commands source can be chosen depending on the value
of respective parameter (password required):
0 = Only local panel
1 = Only Remote Control
2 = Both