Operating Manual LP 33U Series 10 & 20 kVA / S1

1. Insert the “rectifier input fuses - F1, F2, F3”.

2. Switch-ON the utility voltage from the input distribution (both rectifier and bypass if separated).

Overall test results

Test1 OK

Test7 OK

Test2 OK

Test8 OK

Test3 OK

Test9 OK

Test4 OK

Test10 OK

Test5 OK

Test11 OK

Test6 OK

The UPS performs a SELFTEST.

A successful termination of the tests will be indicated with Overall

test results “OK”.
Commissioning cannot be continued should one or more tests result
to be negative.

Please contact in this case your Service Center.

At this stage the electronic power supply is switched ON and the

buzzer sounds.

LED 1 (utility rectifier OK) and LED 2 (utility bypass OK) must be lit.

Press “MUTE” key to reset acoustical alarm. LED Alarm remains lit.


During the first commissioning LP 33U Series requests a set up of the UPS configuration parameters
presented in the following screens.

Without such configuration it is not possible to continue with the commissioning procedure.

WARNING !

The setup of the UPS configuration parameters must be done only by QUALIFIED
AND TRAINED PERSONNEL.
The setup of mistaken values could compromise the integrity and reliability of the
UPS.


In this mode the keys perform the following functions:



Confirm the selection made and select the next parameter.

ESC

Re-establish default value.

Modify or insert the selected value.

Save the configuration of set parameters.


`

Configuration

DISPLAY CONFIGURATION

Select language

:

ENGLISH


ESC



DISPLAY CONFIGURATION screen

Select language
This parameter allows the choice of language used to display

the information.


`

Configuration

UPS CONFIGURATION

Input frequency

:

60

Hz

Output frequency

:

60 Hz

Inverter voltage

:

120

V


ESC



UPS CONFIGURATION screen

Input frequency
Input frequency value (*60Hz).

Output frequency
Inverter output frequency value (*60Hz).

Inverter voltage
Output voltage PHASE/NEUTRAL of the inverter (120 V).

*

Configuration of the frequency to 50Hz requires the intervention of a Service Center.