OPM_LPS_3UO_10K_20K_1US_V010.doc

Operating Manual LP 33U Series 10 & 20 kVA / S1

7.2 PROCEDURES FOR LP 33U Series PARALLEL SYSTEM

7.2.1 LP 33U Series Parallel System start-up

WARNING

!

Before connecting hazardous voltages, make sure that:
The connection to the electrical system has been performed by qualified personnel;
The equipment frame has been correctly grounded to the main earth;
Make sure that utility input protection is removed;
All the panels removed to allow the UPS connection have been correctly reinstalled;
The UPS switches Q1 and Q2 are OFF (Pos. 0);
The input fuses rectifier F1, F2, F3 and battery fuses F9, F10, F11 / F13, F14, F15 are

removed.

This procedure must be performed for the first start-up following the installation, with all the UPS units
completely switched Off and not powered.

This procedure presupposes that the load is not yet supplied by the UPS Parallel System.

NOTE !

The UPS Parallel System can be started-up using the battery supply in case the input
utility
should be unavailable.
To avoid an incidental battery
discharge, it is recommended to proceed to the UPS
Parallel System
start-up having the input utility available.

Open the front door on all UPS units and make sure that:

All the connections to the input/output terminals of the UPS have been made correctly.

The safety screens are fixed in their position.

The switches Q1 and Q2 are open (Pos. O) and the Rectifier input fuses - F1, F2, F3” and “Battery
fuses - F9, F10, F11 / F13, F14, F15
are removed.

Q1 UPS output switch
Q2 Manual

bypass

switch

LEDs on synoptic diagram

LED 1 Utility rectifier OK

LED 2 Utility bypass OK
LED 3 Rectifier ON
LED 4 Discharging battery

LED 5 Booster ON
LED 6 Charge battery ON

LED 7

Inverter available

LED 8

Inverter ON

LED 9

Q1 closed

LED 10 Automatic bypass ON

LED 11 Manual bypass Q2 ON
LED 12 Load on UPS

Input fuses rectifier

Battery fuses

(F13-F14-F15 are only for

LP 33U series / 20 kVA)

Key Key Key LED LED LED

Inverter ON

Inverter OFF

Total Off

Stop Operation

Alarm

Operation

Continue