Operating Manual LP 33U Series 10 & 20 kVA / S1

`

Configuration

BATTERY CONFIGURATION

Type :

Lead Acid

Float voltage

:

164 V

Recharge current

:

004.8 A

Autonomy time

:

009 min

Stop Operation time

:

003 min

Capacity :

0024

Ah

Cells

:

72

ESC



BATTERY CONFIGURATION screen

Type

Battery type (Lead Acid).

Lead - Acid

Sealed Battery (VRLA).

Float voltage

Voltage to maintain battery charging (insert the value of single battery string).
Float voltage = Number of battery cells x battery float voltage per cell.

Typical battery float voltage per cell (ask the battery manufacturer for confirmation):

Lead - Acid (VRLA):

2.27 Vdc for cell

72 cells x 2.27 Vdc = 164 Vdc

Recharge current

Maximum battery recharge current.

Default setting value:

2.4 A (10 kVA)

4.8 A (20 kVA)

Autonomy time

The autonomy time of the battery.

UPS autonomy on battery mode at full load condition.
This value is calculated based on the battery type, capacity and number of cells.

Autonomy times for lead acid batteries (VRLA)

2 x 72 cells

Autonomy at full load at PF=0.8

U floating = 164 Vdc (2.27 Vdc - cell)

Battery with expected trickle life 5 years

UPS Model

12Ah

28Ah (2 x 12Ah)

LP 33U Series / 10 kVA

9 26

LP 33U Series / 20 kVA -

9

Autonomy time for battery supplied by GE UPS manufacturer.

Stop Operation time
Residual battery autonomy time before UPS forced shutdown. Standard set 3 minutes.
Settable from 1 minute to autonomy time in minutes (see tables).

Capacity
Ah capacity of the battery.

Cells
Number of cells of the battery (insert the value of single battery string).

Lead - Acid (VRLA):

72 cells.

NOTE !

The values indicated above, must be considered as standard values.
The actual programmed values must be the ones defined from the battery manufacturer.


`

Configuration

CONFIGURATION

Save and exit ?


Yes


CONFIGURATION screen

Screen to save the configuration of set parameters.

Any additional modification of setup parameters can be done
only by a GE SERVICE PERSON as it requires an access code.