GE Industrial Solutions LP 33U Series 10 & 20 kVA Operating Manual User Manual

Page 35

Advertising
background image

Modifications reserved

Page 35/63

OPM_LPS_3UO_10K_20K_1US_V010.doc

Operating Manual LP 33U Series 10 & 20 kVA / S1

`

Home\Setup\User

MODEM

Tel 2

:

2

Tel 2 enabled

:

N

Tel 3

:

3

Tel 3 enabled

:

N

Tel 4

:

4

Tel 4 enabled

:

N

V

Modem screen 2

Tel 2

It records the second dial-out number.

Tel 2 enabled

This parameter Y/N specifies if the

second telephone number will be used for dial-out.

Tel 3

It records the third dial-out number.

Tel 3 enabled

This parameter Y/N specifies if the third

telephone number will be used for dial-out.

Tel 4

It records the fourth dial-out number.

Tel 4 enabled

This parameter Y/N specifies if the fourth telephone number will be used for dial-out.

`

Home\Setup\User

DISPLAY

UPS name

:

LP Series

Language

:

ENGLISH

V

LCD Display screen

UPS Name

The user can choose the name of the UPS
model shown on the main page (max. 9

characters).

Language

This parameter allows the choice of
language used to display the information.

Valid choices are: English, German, Italian, Spanish, French,
Finnish, Polish, Portuguese, Czech, Slovakian, Chinese,
Swedish, Russian and Dutch
.

`

Home\Setup\User

ECO MODE

Enabled :

N

DAY OF WEEK

d1 d2

d3

d4

d5

d6

d7

HOURS / DAY

24 24 12 12 12 12 12

ECO MODE screen

This screen is enabled only for a single UPS, not for an RPA

Parallel System.

Enabled
This parameter (values Y/N) enables or disables the

operation in ECO Mode.
If the value is Y and the current time is in the interval for the
current day, the ECO Mode is active.
The activation / deactivation of ECO Mode is indicated each
time in the event list.

In order to check the inverter function, at least 1 minute of VFI mode must be programmed during the week (the
Y/N parameter is automatically disabled if this condition is not satisfied).

In case this minimum time in VFI mode is not respected, the ECO Mode will be disabled.
If the value is N, the UPS is normally operating in VFI / double conversion mode at all times.

DAY OF WEEK (d1 to d7): Enabling time in function of weekdays
For the weekdays from d1 to d7 (Saturday to Friday) the edit mode (edit day) allows to define time intervals when
the UPS is operating in ECO Mode.

The hour is given in 24-hour format.

These intervals are defined by:

ECO Mode START:

The hour of the day after which the ECO Mode is enabled.
The ECO Mode is enabled until the following ECO Mode STOP time is reached (the ECO Mode
STOP
time of the same day if this is later than the ECO Mode START time, the ECO Mode

STOP time of the following day otherwise).

ECO Mode STOP:

The hour of the day before which the ECO Mode is enabled.

The ECO Mode is enabled starting from the preceding ECO Mode START time (the ECO Mode START time of the
same day if this is earlier than the ECO Mode STOP time, the ECO Mode START time of the previous day otherwise).

Identical times for ECO Mode START and ECO Mode STOP maintain the existing mode only in case the previous

command was ECO Mode START and the following command will be ECO Mode STOP.

HOURS / DAY:

The number of ECO Mode hours per weekday (from d1 - Saturday to d7 - Friday) is displayed in the operation
mode parameter window (ceiling value).