8 OPTIONS

8.1 OPTIONS GENERAL VIEW

Utility Input

Load

RPA kit
Redundant Parallel Architecture

Allows extending the unit to a parallel system with 2, 3, or 4 units connected on the same bus,

which ensure the highest reliability rate and increase the power availability without prior

investments.

Battery Extension Packs

Extended run-time versions are equipped with additional batteries housed in the UPS itself, to

increase the back-up time of the UPS when the utility fail.

Additional battery cabinets

Depending on model the battery extensions can be housed in additional cabinets with the
same design of the UPS cabinet, delivered with the necessary protection and connection

material.
For extended run-time versions and additional cabinets see enclosed Data Sheets.

Additional battery charge

For battery with extended backup time (max. 8.2 A).

S

G

T

40

00_c

us

tom

er

in

ter

fac

e_02

123

45

67

89

1

0

1

1

16

15

14

13

12

22

21

20

19

18

17

2
1

Customer Interface

The Customer Interface allows the client the exchange of information (monitoring and control)

with the following interfaces:
-

Serial port RS232.

-

6 programmable output channels.

-

2 programmable input channels, of witch one for GEN-ON.

-

EPO (Emergency Power Off).

Advanced SNMP Card
Simple Network Management Protocol

The Advanced SNMP Card is an Interface to the Ethernet Network, and provides UPS

information via the standard SNMP protocol.
The UPS can therefore be managed by a Network Management System (NMS) or by our
applications (for instance JUMP), which uses this information to determine the state of the UPS

in order to guarantee safe and orderly shutdown of the server, when needed.

GE Power Diagnostics

GE Power Diagnostics is an anytime, anywhere concept in UPS status monitoring and alarm

notification that has been successfully implemented in numerous of installations supporting

up to multi-hundred UPS.
Based on the leading Intelligent Remote Information System IRIS all GE UPS types as well as 3rd

party UPS are supported.

Accessing the latest site information via Web and being alerted by Email, SMS or Fax, it
enables the user to make timely decisions in case of changing critical conditions.

With comprehensive data collection and analysis IRIS is not only a remote monitoring &

diagnostics (RM&D) system but, the core of the integrated service offering GE Power
Diagnostics
.

GE Data Protection

GE Data Protection software can communicate with the UPS over RS-232, USB or SNMP to

receive status information and measurement values of the UPS.

In case of a critical condition (time on battery, remaining battery autonomy time or low

battery) for the load, the software starts a controlled shutdown.

An enhanced alarm management system provides the possibility to start applications, send
messages, and send e-mails for every upcoming or disappearing alarm.