7.2.6 Complete Parallel System shutdown

As a result of this procedure the Parallel System is completely switched OFF and not powered.

NOTE !

Follow this procedure only in case the Parallel System and the load must be
completely powered-down.


1. Press “Total Off” key on anyone of the parallel units.

2. Open the output switch Q1 (Pos. 0) on all UPS units.

3. Remove the “rectifier input fuses - F1, F2, F3” and the “battery fuses - F9, F10, F11 / F13, F14, F15”

(remove the external battery fuses in case of external battery) on all UPS units.

The acoustical alarm is activated, press “MUTE” key to reset it.

4

. In order to discharge the DC link capacitors, insert the inverter by pressing Inverter ON ( I ) key

on all UPS units.

`

Home\Meter

INVERTER

f :

60.0

Hz

L1 :

7

V

L2 :

7

V

L3 :

7

V

T :

OK

SYNCHRONIZED

Remark:
Command INVERTER ON will be enabled only when the inverter

voltage of each phase decreases below 7 Vac (about 30 seconds).

`

Home\Meter

BOOSTER

f :

60.0

Hz

L1 :

120

V

L2 :

120

V

L3 :

120

V

Vp :

5

V

Vn :

5

V

Before proceeding to step 5, check on the display panel that the DC
link voltage
(both polarities) Vp and Vn has reached the max.
voltage of 5 Vdc (about 30 seconds).


The acoustical alarm is activated, press “MUTE” key (from Home
screen) to reset it.

5. Disconnect the inverter, on all UPS units, by pressing Inverter OFF ( O ) key and hold until the

LED Inverter (7) turns OFF.

6. Switch OFF the utility power, on all UPS units, at the AC input distribution panel.

END OF PROCEDURE


WARNING !

If the above procedure is not completely performed, it could cause
serious damages to the UPS.
In case the procedure described on step “4 - Discharge DC link capacitors”
cannot
be completely performed, the DC capacitors could be charged with dangerous
voltage for a minimum of 5 minutes.
Wait until capacitors are completely discharged before starting the UPS again.
Apart from the front door, do not open any other part of the UPS.