GE Industrial Solutions LP 33U Series 10 & 20 kVA Operating Manual User Manual

Page 37

Advertising
background image

Modifications reserved

Page 37/63

OPM_LPS_3UO_10K_20K_1US_V010.doc

Operating Manual LP 33U Series 10 & 20 kVA / S1

Example 5:

An equivalent set of parameters for Example 4 is.

Weekday

d1

- Saturday

d2

- Sunday

d3

- Monday

d4

- Tuesday

d5

- Wednesday

d6

- Thursday

d7

- Friday

ECO Mode START

00:00 00:00 18:00 18:00 06:00 09:00 12:00

ECO Mode STOP

23:59 20:00 18:00 06:00 06:00 09:00 13:00

ECO Mode START

ECO Mode STOP



The ECO Mode is active from 18:00 of weekday d3 - Monday until 06:00 of weekday d4 - Tuesday (as
indicated by the ECO Mode STOP time of weekday d4 - Tuesday).

The ECO Mode STOP time of weekday d3 - Monday has no effect as it is followed by the ECO Mode STOP
time of weekday d4 - Tuesday.

It can be, without change of meaning, any time between 18:00 and 23:59.

Similarly, the ECO Mode is active from 18:00 of weekday d4 - Tuesday until 06:00 of weekday d5 -
Wednesday
.

The ECO Mode START time of weekday d5 - Wednesday has no effect as it is preceded by the ECO Mode
START
time of weekday d4 - Tuesday.

It can be, without change of meaning, any time between 00:00 and 06:00.


NOTE !

To avoid undesired ECO Mode operation, verify:
Date and Time (first page of parameter).
ECO mode screen how many hours of ECO Mode operation have been selected for

each day of the week.



NOTE !

The ECO Mode will become active only if the load is supplied from the inverter.