Submenu Item

Programmable Range

Default Setting

12Vdc

24Vdc

48Vdc

125Vdc

220Vdc

LVD 1

0-9999999999

10.5V

21.00V 42.00V 101.50V

178.50V

LVC 1

0-9999999999

12.5V 25.00V 50.00V 120.83V

212.50V

Alarm Priority

Major/Minor/Message Major

Relay Mapping

1-16 or N/A

(mapping disabled)

1

Control

Check = enable LVD control

Checked

Alarm cutoff

Check = allow alarm to be cutoff

Not checked

LVD 2

0-9999999999

10.5V

21.00V 42.00V 101.50V

178.50V

LVC 2

0-9999999999

12.5V 25.00V 50.00V 120.83V

212.50V

Alarm Priority

Major/Minor/Message Major

Relay Mapping

1-16 or N/A

(mapping disabled)

2

Control

Check = enable LVD control

Checked

Alarm cutoff

Check = allow alarm to be cutoff

Not checked

LVD 3

0-9999999999

10.5V

21.00V 42.00V 101.50V

178.50V

LVC 3

0-9999999999

12.5V 25.00V 50.00V 120.83V

212.50V

Alarm Priority

Major/Minor/Message Major

Relay Mapping

1-16 or N/A

(mapping disabled)

3

Control

Check = enable LVD control

Checked

Alarm cutoff

Check = allow alarm to be cutoff

Not checked

LVD 4-10

0-9999999999

10.5V

21.00V 42.00V 101.50V

178.50V

LVC 4-10

0-9999999999

12.5V 25.00V 50.00V 120.83V

212.50V

Alarm Priority

Major/Minor/Message Major

Relay Mapping

1-16 or N/A

(mapping disabled)

N/A

Control

Check = enable LVD control

Not checked

Alarm cutoff

Check = allow alarm to be cutoff

Not checked

LVD Inhibit (Status)

Active/Inactive Inactive

Alarm Priority

Major/Minor/Message Major

Relay Mapping

1-16 or N/A

(mapping disabled)

N/A

Alarm cutoff

Check = allow alarm to be cutoff

Not checked

High Volt. Shutdown

0-9999999999

14.25V 29.50V 58.00V 140.17V

246.50V

Alarm Priority

Major/Minor/Message Major

Relay Mapping

1-16 or N/A

(mapping disabled)

N/A

Control

Check = enable LVD control

Not checked

Alarm cutoff

Check = allow alarm to be cutoff

Not checked

CEMF In-circuit Voltage

0-9999999999

13.70V 27.40V 54.80V 132.43V

232.90V

Bypass Voltage

0-9999999999

13.55V 27.10V 54.20V 130.98V

230.35V

Alarm Priority

Major/Minor/Message Major

Relay Mapping

1-16 or N/A

(mapping disabled)

N/A

Control

Check = enable LVD control

Not checked

Alarm cutoff

Check = allow alarm to be cutoff

Not checked

Table J–Controls menu defaults