Page 119 of 122

0x010C Signal_6_In_Signal_Table_4 Custom Signal 6 (x100)

4 (signed int_32)

0x010E Signal_7_In_Signal_Table_4 Custom Signal 7 (x100)

4 (signed int_32)

0x0110 Signal_8_In_Signal_Table_4 Custom Signal 8 (x100)

4 (signed int_32)

0x0112 Signal_9_In_Signal_Table_4 Custom Signal 9 (x100)

4 (signed int_32)

0x0114 Signal_10_In_Signal_Table_4 Custom

Signal 10 (x100)

4 (signed int_32)

-- --

--

0x0040 * S

Signal_1_In_Signal_Table_S

Read Signal 1 in Signal table S (x100)

4 (signed int_32)

-- --

--

0x0040 * S +
((SS-1) *2)

Signal_SS_In_Signal_Table_S

Read Signal SS in Signal table S (x100)

4 (signed int_32)

-- --

--

0x0182 Signal_1_In_Signal_Table_5 Timer 1

4 (signed int_32)

0x0184 Signal_2_In_Signal_Table_5 Timer 2

4 (signed int_32)

0x0186 Signal_3_In_Signal_Table_5 Timer 3

4 (signed int_32)

0x0188 Signal_4_In_Signal_Table_5 Timer 4

4 (signed int_32)

0x018A Signal_5_In_Signal_Table_5 Timer 5

4 (signed int_32)

0x018C Signal_6_In_Signal_Table_5 Timer 6

4 (signed int_32)

0x018E Signal_7_In_Signal_Table_5 Timer 7

4 (signed int_32)

0x0190 Signal_8_In_Signal_Table_5 Timer 8

4 (signed int_32)

0x0192 Signal_9_In_Signal_Table_5 Timer 9

4 (signed int_32)

0x0194 Signal_10_In_Signal_Table_5 Timer 10

4 (signed int_32)

-- --

--

0x01C2

Signal_1_In_Signal_Table_6

Counter 1

4 (signed int_32)

0x01C4

Signal_2_In_Signal_Table_6

Counter 2

4 (signed int_32)

0x01C6

Signal_3_In_Signal_Table_6

Counter 3

4 (signed int_32)

0x01C8

Signal_4_In_Signal_Table_6

Counter 4

4 (signed int_32)

0x01CA

Signal_5_In_Signal_Table_6

Counter 5

4 (signed int_32)

0x01CC

Signal_6_In_Signal_Table_6

Counter 6

4 (signed int_32)

0x01CE

Signal_7_In_Signal_Table_6

Counter 7

4 (signed int_32)

0x01D0

Signal_8_In_Signal_Table_6

Counter 8

4 (signed int_32)

0x01D2

Signal_9_In_Signal_Table_6

Counter 9

4 (signed int_32)

0x01D4

Signal_10_In_Signal_Table_6

Counter 10

4 (signed int_32)

Table P–CXC Modbus PDU address definition for function code 0x03 (read holding registers)

PDU Address

Variable Name

Variable Description

Response Data Format

0x0001

Relays_Total (Y)

Read number of relays

BINARY

0x0002 Total_Active_Alarms

(Z)

Read total active alarms

BINARY

0x0003

System_Major_Alarm

Read system major alarm status

BINARY

0x0004

System_Minor_Alarm

Read system minor alarm status

BINARY

-- --

--

0x0011

Alarm_Tables_Total (X)

Read number of alarm tables (X<=0x1E)

BINARY

0x0012

Alarms_Total_In_Alarm_Table _1 (A1)

Read number of alarm in alarm table 1
(A1 <= 0x3F)

BINARY

0x0013

Alarms_Total_In_Alarm_Table _2 (A2)

Read number of alarm in alarm table 2
(A2 <= 0x3F)

BINARY

-- --

--

0x0011 + X

Alarms_Total_In_Alarm_Table _X (AX)

Read number of alarm in alarm table X
(AX <= 0x3F)

BINARY

-- --

--

0x0031

Number_of_Active_Alarms_In_Alarm_table _1

Read number of active alarms in alarm table 1

BINARY

0x0032

Number_of_Active_Alarms_In_Alarm_table _2

Read number of active alarms in alarm table 2

BINARY

-- --

0x0031 + (X-1)

Number_of_Active_Alarms_In_Alarm_table _X

Read number of active alarms in alarm table X

BINARY