4.3.4.11 Battery Discharge Test Completion

The test is considered complete once the battery begins to charge. This could be due to the test
ending from timeout, the system reaching the end (termination) voltage or an abort condition.

Once the battery begins to charge, the recharge cycle begins. Live battery recharge information
is available from the battery log web page.

4.3.4.12 Remote BT Mode

This feature will force a transition to BT mode when a user-defined condition (custom alarm) is
true.

When this condition is true, BT mode is entered regardless of the regular safety checks that are
performed during manual or automatic changes to BT mode. BT mode stays active as long as
the condition remains true.

A check box is used to enable/disable this feature. The default is disabled. If the condition is
true and the check box is disabled, then the system will be put into FL mode.

If the condition becomes false, disabled, invalid, or the (assigned custom alarm) equation is
empty, the system will be put into FL mode.

NOTE: This feature is exclusive for the Cordex series of rectifiers. If Remote BT is

active and a rectifier other than the Cordex series is added to the system then
Remote BT will be aborted.