Alpha Technologies Cordex Controller Ver.2.0 User Manual

Page 44

Advertising
background image

Refer to the back of this manual for Factory Service and Technical Support contact information

Alpha Technologies Ltd.

034-136-C0 Rev B WC

Printed in Canada. © 2010 Alpha Technologies Ltd. ALPHA and CORDEX are trademarks of Alpha Technologies Ltd. All Rights Reserved.

Page 42 of 122

6.4.4

Battery Monitor

6.4.4.1

Enable

This menu item enables the Supervisor to control the CXC’s battery monitor feature.
Battery Properties section must be completed to enable this feature.

6.4.4.2

Load Type

This menu item enables the Supervisor to select the type of load on the system: constant
power, current, or resistive. This is used for battery capacity calculations.

6.4.4.3

Disconnect Voltage

The disconnect voltage should be set to the value of the LVD that will disconnect the battery
from the load. The Battery Runtime algorithm uses this value to calculate the hours remaining
during an AC outage.

6.4.4.4

Reset Battery Monitor

The Battery Monitor should be reset when installing new or different batteries.

6.4.4.5

Battery Properties (See 6.4.8)

The “Battery Properties” button at the bottom of the Battery Monitor window is a link to the
Battery Properties window.

The return path (the menu structure) will remain intact; i.e., the user will return through the
window where the Battery Properties button was tapped.

6.4.5

Battery (Discharge) Test

The Battery Test (BT) is used to update the status of the battery capacity. It can be set to run automatically or can
be initiated manually (via Mode Selection button). See 4.3.4 for more details.

6.4.5.1

BT End Voltage

This menu item controls the end (or termination) voltage of the BT; +0.5V above Rectifier BT
Voltage is recommended.

Rectifier BT Voltage (identical to 6.3.2.3 – a change in one alters the other)
This menu item enables the Supervisor to set the Rectifier BT Voltage to the desired value
during the test (mode). This setting should have a minimum of LVD + 1V.

Rectifier BT Timeout (identical to 6.3.2.11 – a change in one alters the other)
This menu item controls the duration of the Battery Test.

6.4.5.2

Auto-BT

Enable
This menu item enables the Supervisor to control the CXC’s Auto-BT feature.

Interval
This menu item enables the Supervisor to program the time, in days, between Auto Battery
Tests.